2 psi above the CRD (3) set point. The relief the 90-21 set pressure for 1-1/2" thru 8" valve sizes and 2 psi for 10" and valve for the 10" and 12" 90-21 should be installed a recommended min- 12"...
Page 4
93480 90-21 Model Pressure Reducing Valve "Underwriters Laboratories Listed" UL listed model numbers: 90G-21, Globe 90A-21, Angle INLET OUTLET Note: For steel and ductile iron 300 valves, use CRDKX [with special All sizes, KX = Red paint diaphragm washer, yoke, and...
93480 90-21 Model Pressure Reducing Valve "Underwriters Laboratories Listed" Pressure Reducing Feature Pressure reducing control (3) is a normally open control that responds to main valve outlet pressure changes. An increase in outlet pressure tends to close control (3) and a decrease in outlet pressure tends to open control (3). This causes main valve cover pressure to vary and the main valve modulates (opens and closes), maintaining a relatively constant outlet pressure.
Page 6
93480 90-21 Model Pressure Reducing Valve "Underwriters Laboratories Listed" Ductile iron/Cast steel: Class 150, DI: 250 psi max ULC Listed Class 150, STL: 285 psi max Ductile iron valve: Class 300, DI/STL: 300 psi max Class 150: 250 psi max...
Reducing Valve Description The Model 100-01 Hytrol Valve is the main valve for the CIa-VaI Model 90-21 Pressure Reducing Control Valve. It is a hydraulically operated, diaphragm-actuated, globe or angle pattern valve. This valve consists of three major components; body, di- aphragm assembly, and cover.
1. Shut off pressure to the 90-21 valve by slowly closing upstream and is loose on the stem. In either case, this is sufficient cause to remove downstream isolation valves.
Page 9
2. Re-install the pilot system and tubing exactly as it was prior to ing. Line up the diaphragm holes with the stud or bolt holes on the removal. body. On larger valves with studs, it may be necessary 3. Follow steps under "Start-Up and Adjustment" Section in N- 90-21 UL Sheet.
When ordering please specify: All nameplate data, Description, Item number CLA-VAL 1701 Placentia Ave • Costa Mesa CA 92627 Phone: 949-722-4800 • Fax: 949-548-5441 • E-mail: info@cla-val.com • www.cla-val.com N-100-01 UL (R-09/2019) Copyright Cla-Val 2019 Printed in USA Specifications subject to change without notice.
EQUAL TO AN ACCEPTABLE PLUS OR MINUS 15 PSI OF SETPOINT. CLA-VAL 1701 Placentia Ave • Costa Mesa CA 92627 Phone: 949-722-4800 • Fax: 949-548-5441 • E-mail: info@cla-val.com • www.cla-val.com N-90-21 UL Performance Characteristics (R-09/2019) Copyright Cla-Val 2019 Printed in USA Specifications subject to change without notice.
This warranty shall not apply if the product has been RESPONSIBILITY altered or repaired by others, and Cla-Val. shall make no We will not be responsible for delays resulting from strikes, allowance or credit for such repairs or alterations unless accidents, negligence of carriers, or other causes beyond our control.
Page 19
Cla-Val shall not be liable for any incidental or consequential 2. Cla-Val reserves the right to refuse the return of any products. loss, damage or expense arising directly or indirectly from 3. Products more than six (6) months old cannot be returned for cred- the use of the product.