Frames Mr7 And Mr8 - Honeywell SmartDrive HVAC Installation Manual

Variable frequency drive for heating, ventilation and air conditioning applications
Table of Contents

Advertisement

C
OMMISSIONING
6.3.2

Frames MR7 and MR8

Follow the procedure described above to modify the EMC protection of the drive of frames MR7
and MR8 to EMC-level C4.
Remove the main cover of the drive and locate the jumper. MR8 only: Push down
1
the grounding arm. See Figure 53.
Figure 53.
MR7 and MR8: Locate the EMC box under the cover. Remove the screws of the
2
box cover to expose the EMC-jumper. Detach the jumper and re-fix the box cover.
Figure 54.
Honeywell
• 62