3.1 GENERAL TECHNICAL DATA
SIZE
NECS-ME /B
COOLING
Cooling capacity
Total power input (unit)
EER
ESEER
Heat exchanger water flow
Heat exchanger pressure drop
COMPRESSORS
Number
Number of capacity
Number of circuits
Type of regulation
Minimum capacity steps
Type of refrigerant
Refrigerant charge
Oil charge
NOISE LEVELS
Total sound power
Total sound pressure
DIMENSIONS AND WEIGHTS
Length
Width
Height
Weight
1
Plant (side) cooling exchanger water (in/out) 12/7 °C
Condensation temperature 47 °C
2
Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units;
in compliance with ISO 3744 for non-certified units
Average sound pressure level, at 10 (m.) distance, unit in a free field on a reflective surface; non-binding value obtained
from the sound power level
3
Standard configuration
-
Not available
ELCADOC - Ver. 1.0.0.1
NECS-ME
B
0152
0182
(1)
kW
39,5
45,8
kW
12,0
13,5
3,29
3,39
-
-
m³/h
6,80
7,89
kPa
48,0
41,3
N°.
2
2
N°.
2
2
N°.
1
1
STEPS
STEPS
%
50
50
R410A
R410A
kg.
-
-
kg.
3
3
(2)
dB(A)
73
74
dB(A)
42
43
(3)
mm.
1130
1130
mm.
669
669
mm.
1255
1255
kg.
270
280
5
NECS-ME_0152_1604_201004_
0202
0252
0262
53,6
60,5
67,4
15,7
18,1
20,0
3,41
3,34
3,37
-
-
-
9,23
10,4
11,6
41,0
39,1
48,4
2
2
2
2
2
2
1
1
1
STEPS
STEPS
STEPS
50
50
50
R410A
R410A
R410A
-
-
-
3
3
3
74
74
75
43
43
44
1130
1130
1130
669
669
669
1255
1255
1255
290
295
300
0302
0352
80,2
92,8
23,4
26,9
3,43
3,45
-
-
13,8
16,0
29,4
27,6
2
2
2
2
1
1
STEPS
STEPS
50
50
R410A
R410A
-
-
3
3
76
77
44
45
1310
1310
893
893
1496
1496
410
500
Ref.: R410A