OPC8017 OPC8024 / OPD8017 OPD8024
ATTENTION
Damage to the electronics!
Condensation can damage the device.
Switch on the device only after it has acclimated to the ambient temperature.
Recommendation for use:
The shielding of a data cable must always be connected with the connector
housing (EMC).
Recommendation for use:
Insofar as they are specified in the scope of delivery or in the replacement parts
list, only connectors and cables offered by ADS-TEC are to be used for
commissioning and during operation. All other connectors and cables which you
use for commissioning and during operation must have been approved.
Check for operational readiness
Make sure that the threaded pins of the clamping blocks are tightened to 0.5 Nm.
Commissioning device
When connecting and disconnecting cables, make sure that no power is being applied to the
device or cables.
Connect the cables in any order.
Connect the cables to the strain relief fixtures
Make sure that the 24 V power supply complies with NEC Class 2.
Switch on the device by connecting the power adapter to the external power supply.