Toshiba MMD-AP 1HF2UL Series Manual page 15

Outside air unit type
Table of Contents

Advertisement

E15-3S2
6-4. Basic operation
Use conditions
In "COOL" mode, if temperature of the outside air is under the setup temp. +5.4°F, FAN status is automatically made. When temperature of the outside air is under 66°F,
FAN status is also made regardless of the setup temperature.
In "HEAT" mode, if temperature of the outside air is over the setup temp. -5.4°F, FAN status is automatically made. When temperature of the outside air is over 59°F,
FAN status is also made regardless of the setup temperature.
Case to use in SMMS-e "MMY-MAP___6HT_P-UL" and Side blow SMMS-e "MCY-MHP___7HS-UL"
Outdoor Air Temperature °F
COOL mode
(Outside Air Unit
and Outdoor Unit)
HEAT mode
(Outside Air Unit)
HEAT mode
(Outdoor Unit)
REQUIREMENT
In "COOL" or "FAN" mode, if temperature of the outside air is under 41°F, the operation stop automatically in order to protect the equipment.
In this case, continue the operation by selecting "HEAT" mode.
In "HEAT" mode, if temperature of the outside air is under 23°F, the operation stops automatically in order to protect the equipment.
When operating the air conditioner with the outside air temp. under 23°F (minimum -4°F),
set temp. of the outside air to be taken in to 32 (*1)°F or upper using a duct heater (locally procured).
For details, consult the dealer which you purchased the air conditioner.
(*1) When 096type system with 1 indoor unit, be taken in to 41°F or upper using a duct heater.
) i (
C
a
s
e
f o
s
a t
n
50
41
32
23
14
-13
In "HEAT" mode, if temperature is out of range in the Use condition, the fan of the Outside Air Unit intermittently operate. So take care not to overheat a duct heater,
when use a duct heater.
Please refer to "Outside Air Unit's Owner's Manual" except the above contents.
4 -
14
23
Automatic HEAT
operation starts
-4
23
Using duct heater
Automatic HEAT
operation starts
Outside Air Unit
d
a
d r
s
s y
e t
m
Use condition
-4
5
14
23
32
Outdoor unit temp. [°F]
3
2
5
0
6
8
Setup temp.
4
1
Fan
Setup temp. +5.4°F
Setup temp.
Heating
Setup temp. -5.4°F
Setup temp.
Heating
Setup temp. -5.4°F
Duct heater
Outside air temp.
(locally procured)
(
) i i
C
a
se of 096type system with 1 indoor unit
50
41
32
23
14
-13
15
MMD-AP___1HF2UL
8
6
1
0
4
1
1
5
Cooling
Automatic COOL
operation starts
109
Fan
109
Fan
Use condition
-4
5
14
23
32
Outdoor unit temp. [°F]
1
2
2