Network Component Installation

Once the passive LAN cable plant has been installed and certified, the active Network
components can be installed. These components include switches, repeaters, and media
translators and will be located in wiring closets designed for that purpose.
Warning
The Database Server and Application Server must be connected to a BATTERY
BACKUP outlet of the 1000 VA UPS.
The following components must be connected to the BATTERY BACKUP outlets of a
UPS: (See Figure 2-18)
Up to 3 Clinical Network components -- switches, repeaters, media translators -- may be
connected to a single, 650VA UPS.
It is recommended that Access Points and Harmony Remote Power Supplies also be
connected to a 650 VA UPS.
The following components may be connected to the ACCESSORY outlets of a 650 VA
UPS or to a separate non-UPS electrical outlet with the same ground.
The LaserJet Printer must not be connected to the UPS.
Switch
The switches must be verified to ensure it is running a supported firmware revision. The
Firmware
supported revisions are:
To downgrade to a supported firmware revision, see the procedures beginning on page 5-46.
Device
The next step is to configure the devices - network switches, RangeLAN2 Access Points,
Configuration
Wireless Patient Monitors, and Access Point Controllers. This includes setting their IP
Address. There are two methods of configuring these settings using the Database Server
or another PC or laptop via the ConfigTool (for all devices including switches) or a
HyperTerminal connection (for switches only).
Note
Configuration of all network devices is to be done before they are connected to the network.
all switches
media translators
Harmony Access Point Controller
workstations for all Information Centers and Clients
Philips 2 Channel and 4 Channel Recorders
displays
video splitters
printer spooler
The HP2524 switch: F.02.02 and F.02.13
Cisco 1900 Switch: 9.00.04 & 8.01.02
Network Component Installation