LG PQNFB17C1 Installation & Owner's Manual page 76

Bacnet (acp bacnet)
Table of Contents

Advertisement

FUNCTIONAL SPECIFICATIONS ACP BACnet
66
Local Definition of Object ID - The instance number is a pair, this consists of the indoor unit No. and
item.
Product Type(Indoor:0, Vent:1, AHU:2, ODU:3, AWHP:4, GENERAL:5)
Example of Point Table
The point table below is passed to BMS, and BMS registers the object.
Case Indoor
Product
Address
Type
0
0
0
0
1
0
1
0
15
0
15
0
16
0
16
0
255
0
255
0
Product
Point
No.
No.
0
1
0
2
1
1
1
2
15
1
15
2
16
1
16
2
255
1
255
2
Instance No.
0x00001(1)
0x00002(2)
0x00101(257)
0x00102(258)
0x00F01(3841)
0x00F02(3842)
0x01001(4097)
0x01002(4098)
0x0FF01(65281)
0x0FF02(65282)
Name
ON/OFF : setting
ON/OFF : status
ON/OFF : setting
ON/OFF : status
ON/OFF : setting
ON/OFF : status
ON/OFF : setting
ON/OFF : status
ON/OFF : setting
ON/OFF : status