Mitsubishi Electric MELIPC MI5000 Series User Manual page 155

Startup
Hide thumbs Also See for MELIPC MI5000 Series:
Table of Contents

Advertisement

■Ethernet cables and hubs (during CC-Link IE Field Network Basic configuration)
Use Ethernet cables and hubs that meet the following conditions.
Ethernet cables
Standard
Specifications
100BASE-TX
Category 5 or better, (shielded, STP) straight cable
Category 5 or 5e, (shielded, STP) cross cable
Hubs
Use cables that meet all of the following conditions. Operation cannot be guaranteed if conditions are not met.
• Compliant with IEEE802.3(100BASE-TX) standards
• Incorporating auto MDI/MDI-X function
• Incorporating auto negotiation function
• Switching hub (Layer 2 switch)
*1 Repeater hubs cannot be used.
Wiring procedure
The following shows the procedure for wiring Ethernet cables.
■Connection of Ethernet cables
1.
While paying attention to the connector orientation, insert the Ethernet cable connector into the Ethernet connector of
this product until a click is heard.
2.
Lightly pull on the Ethernet cable to check that it is properly connected.
3.
Make sure that the SPEED LED of the connected connector is lit green.
• The time required after the Ethernet cable is connected until the SPEED LED turns on will vary. This
normally takes several seconds. However, depending on the status of devices on the circuits, link-up
processing may repeat, requiring more time.
• If the SPEED LED does not light, check that there are no problems with the Ethernet cable.
• If Ethernet devices are connected to a network that has a communications rate of 10 Mbps, the SPEED
LED will turn off. Check communications status using PING or similar tools.
■Removal of Ethernet cables
Press and hold the clip on the Ethernet cable connector, and pull it out.
*1
Communication
Connector
s speed
100Mbps
RJ45
APPX
Appendix 10 Wiring
A
153