Installation
• You can select the option for indoor address selection mode only when
Master / Slave is selected.
• You can distribute the using power to maximum of 64 indoor units.
(When showing the stand by power, maximum of 63 indoor units.)
- If the PDI connects to 64 indoor units, set the addresses of indoor units from 00 to 3F.
(Central control address : 00~3F)
Ex) If addresses of indoor units are set by "12", "13", "14" and "15",
set start address by "12" and set end address by "15".
- Press the Menu key to save the remote reading service ID and return to the
initial screen.
18 Power Distribution Indicator
Press the Shift key to enter the
indoor selection mode
LGAP
( S t a r t )
( 0 0 )
( S t a r t )
( 1 2 )
( S t a r t )
( 0 0 )
- >
( E n d )
- >
( 3 F )
- >
( E n d )
- >
( 1 5 )
Initial Screen
- >
( E n d )
- >
( 0 0 )