Bosch Worcester Danesmoor Utility Regular ErP+ 12/18 Installation, Commissioning And Servicing Instruction Manual page 54

Floor standing oil-fired condensing boiler conventional flue & room sealed flue
Table of Contents

Advertisement

Fault finding and diagnosis
Line
5
Burner does not fire, burner locks out after 25 seconds from motor start?
5a
Burner fires when the photo cell is covered?
Photo cell voltage ≥ 3.8V in the dark and
5b
approximately 0V in the light?
6
Pump washing pressure 1 to 2 bar?
6a
Pump pressure more than 6 bar?
6b
Check oil supply to the pump, if oil supply is OK
6c
Drive coupling broken?
7
Ignition spark present?
7a
Are ignition leads and electrodes OK and set correctly?
8
Solenoid coil releases working pressure?
8a
Does burner light or green 0.5 seconds ON/red 0.5 seconds ON
before lockout?
8b
Contaminated fuel filters?
8c
Coil lead OK
Solenoid coil resistance 90 to 110 Ω
8d
8e
After 15 seconds from motor start, 25 to 30 Volts d.c. to solenoid
coil? (coil connected)
9
Air set correctly?
10
Does the burner light?
Flue damper fitted? (if required)
10a
Is the nozzle atomising the fuel?
10b
Nozzle new?
10c
Check oil pipe from pump to nozzle holder
11
Combustion head set correctly?
11a
Flame goes out then re-lights
11b
Boiler or flue blocked
11c
If balanced flue, remove the snorkel and test - now OK?
11d
Balanced flues can recirculate gases causing recycling
Photo cell voltage ≥ 3.8V in the dark and
11e
approximately 0V in the light?
Table 14
54
Check
Yes
Go to line 5a
No
Go to line 6
Yes
Remove extraneous light
No
Go to line 5b
Yes
Replace the control board
No
Replace the photo cell
Yes
Go to line 7
No
Go to line 6a
Yes
Replace oil pump
No
Go to line 6b
Go to line 6c
Yes
Replace drive coupling
No
Replace oil pump
Yes
Go to line 8
No
Go to line 7a
Yes
Replace control box
No
Replace/reset electrodes/ignition leads
Yes
Go to line 9
No
Go to line 8a
Yes
Go to line 5a
No
Go to line 8b
Yes
Clean/Replace filters
No
Go to line 8c
Yes
Go to line 8d
No
Replace solenoid coil lead
Yes
Go to line 8e
No
Replace solenoid coil
Yes
Replace oil pump
No
Replace control box
Yes
Go to line 10
No
Adjust combustion air settings
Yes
Go to line 11
No
Go to line 10a
Yes
Go to line 11
No
Go to line 10b
Yes
Go to line 10c
No
Replace nozzle
Clean/ replace pump and fuel line filters
Yes
Go to line 11a
No
Reset combustion head
Yes
Go to line 11c
No
Go to line 11b
Yes
Clear blockage
No
Go to line 11c
Yes
Go to line 11d
No
Go to line 11e
Check the flue position and seals
Yes
Replace the control box
No
Replace photocell
Greenstar Danesmoor Utility
ErP+
and Utility System
Action
ErP+
- 6 720 821 720 (2018/04)