Boiler Installation; Flue Installation - Bosch Worcester Danesmoor Utility Regular ErP+ 12/18 Installation, Commissioning And Servicing Instruction Manual

Floor standing oil-fired condensing boiler conventional flue & room sealed flue
Table of Contents

Advertisement

Installation
5.3

Boiler installation

1. Lift the front of the top panel (A) upwards to disengage the ball stud
connections (B) and pull forwards to release from the brackets (C) at
the back to remove. Pull front panel (D) forward from the bottom and
near the top disengaging the ball studs from their connections (E)
and lift off the ledge (F) that runs along the bottom of the fascia to
remove.
2. Unplug burner lead (G) from control box.
2.
G
D
1.
I
Fig. 36 Boiler installation
Utility system only:
▶ In the case of the Utility system boiler, remove the retaining screw
[1] at the base of the expansion vessel.
▶ Pull the expansion vessel forward slightly and down to remove.
Place to expansion vessel outside of the boiler, taking care not to kink
or stretch the flexible hose.
Fig. 37
26
1.
A
C
B
E
E
E
6720809436-12.1Wo
1
3. Unscrew to loosen the retaining ring (H) that secures the flexible air
supply tube to the burner and pull the flexible air supply tube free
from the burner (see figure 38).
3.
Fig. 38
▶ Undo and remove the retaining nut (J) on top of the burner. The
burner mounting (K) can now be eased off the lug (L) on the burner
collar to remove the burner from the heat exchanger. Store the
burner and retaining nut safely away from the boiler.
▶ Carefully move the boiler into position observing at all times the
correct method for handling heavy objects.
5.4

Flue installation

The flue can exit the boiler from outlets A, B, C or D allowing vertical (RS)
and horizontal (RS low or high level) flues to be fitted. (CF position 'A'
only).
Refer to the separate flue installation instructions supplied with the flue
kits available for this boiler:
A
B
D
C
5
L
1
2
3
Fig. 39
[1]
Boiler outer casing
[2]
Outer flue tube
[3]
Outlet/elbow connection
[4]
Outside wall/roof
[5]
CF adaptor
[L]
Effective length of the flue
Greenstar Danesmoor Utility
ErP+
and Utility System
H
K
J
4
120mm
1
4
3
ErP+
- 6 720 821 720 (2018/04)
L
600mm
(min)