The maintenance-free microprocessor-controlled room sensor AERASGARD
CO
content of the air within a range of 0...2000 ppm and the temperature within a range of 0...+50°C. The measured values are converted into
2
standard signals of 0 -10 V.
The maintenance-free microprocessor-controlled room sensor AERASGARD
(can be deactivated via DIP switches) is used for detecting the overall room climate. It measures CO
quality (VOC) in one of three sensitivity levels that can be selected LOW / MEDIUM (default) / HIGH, temperature within a range of 0...+50°C as well as
relative humidity of 0...100 % r.H. The measured values are converted into standard signals of 0 -10 V oder 4...20 mA (selectable via DIP switches). As an
option, the measured values can be shown continuously in the illuminated display.
Elegant enclosure made of plastic, with snap-on lid, base with 4-hole attachment, for installation on vertically or horizontally installed in-wall flush boxes,
with predetermined breaking point for on-wall cable entry.
The relative humidity (% r.H.) quotient of water vapour partial pressure divided by the saturation vapour pressure at the respective gas temperature.
A digital, long-term stable sensor used as measuring element for relative air humidity and temperature guarantees exact measurement results. The air
quality is determined based on a (VOC) gas mixture sensor. The CO
technology).
TECHNICAL DATA
Voltage supply:
Power consumption:
Outputs:
Relay output:
HUMIDITY
Sensors:
Measuring range, humidity:
Operating range, humidity:
Deviation, humidity:
Output, humidity:
TEMPERATURE
Measuring range, temperature:
Operating range, temperature:
Temperature deviation:
Output, temperature:
AIR QUALIT Y (VOC)
Sensor, VOC :
Measuring range, VOC :
Output, VOC :
Measuring accuracy, VOC :
Service life:
CARBON DIOXIDE (CO
)
2
Sensor, CO
:
2
Measuring range, CO
:
2
Output, CO
:
2
Measuring accuracy, CO
:
2
Temperature dependence, CO
2
- W ⁄ RLQ - CO
- W ⁄ RFTM - LQ - CO
2
2
24 V AC ⁄ DC (± 10 %)
RCO
- W ⁄ RTM - CO
- SD :
2
2
< 1.5 W ⁄ 24 V DC typical; < 2.9 VA ⁄ 24 V AC typical; peak current 200 mA
RLQ - CO
- W ⁄ RFTM - LQ - CO
2
< 4.4 W ⁄ 24 V DC typical; < 6.4 VA ⁄ 24 V AC typical; peak current 200 mA
RTM - CO
- SD 0 -10 V (fixed)
2
Rx x - CO
- W
0 -10 V or 4...20 mA, working resistance < 800 Ω
2
(selectable via DIP switches, selected variant applies for all outputs),
with offset potentiometer (± 10 % of the measuring range)
RTM - CO
- SD without changeover contact
2
Rx x - CO
- W
with potential-free changeover contact (24 V / 1 A)
2
(assignment selectable via DIP switches, switchpoint adjustable)
digital humidity sensor with integrated temperature sensor,
low hysteresis, high long-term stability
0...100 % r. H.
0...95 % r. H. (without dew formation)
typically ± 2.0 % (20...80 % r. H.) at +25 °C, otherwise ± 3.0 %
0 -10 V or 4...20 mA (selectable via DIP switches)
0...+ 50 °C
0...+ 50 °C
± 0.2 K at +25 °C
RTM - CO
- SD 0 -10 V (fixed)
2
Rx x - CO
- W
0 -10 V or 4...20 mA (selectable via DIP switches)
2
VOC sensor (metal oxide) (VOC = volatile organic compounds),
with manual calibration (via zero button) and
with automatic calibration (can be deactivated via DIP switches)
0...100 % air quality; referred to calibrating gas;
multi-range switching (selectable via DIP switches)
VOC sensitivity low, medium, high
0 -10 V (0 V = clean air, 10 V = polluted air) or 4...20 mA
(selectable via DIP switches, switchpoint can be adjusted from 0...100 % of the output signal)
± 20 % of final value (referred to calibrating gas)
> 60 months (under normal load conditions)
optical NDIR sensor (non-dispersive infra-red technology),
with manual calibration (via zero button),
RTM - CO
- SD with automatic calibration (fixed)
2
Rx x - CO
- W
with automatic calibration (can be deactivated via DIP switches)
2
RTM - CO
- SD 0...2000 ppm (fixed)
2
Rx x - CO
- W
0...2000 ppm or 0...5000 ppm (selectable via DIP switches)
2
RTM - CO
- SD 0 -10 V (fixed)
2
Rx x - CO
- W
0 -10 V or 4...20 mA (selectable via DIP switches)
2
± 30 ppm ± 3 % of measured value
:
± 5 ppm ⁄ °C or ± 0.5 % of measured value ⁄ °C
(whichever is higher)
- W ⁄ RTM - CO
2
®
RTM - CO
- SD with automatic calibration (fixed) is used for detecting the
2
®
RFTM - LQ - CO
- W and RCO
2
content of the air is measured using an optical NDIR sensor (non-dispersive infra-red
2
- W :
2
10
- SD
2
- W / RLQ - CO
- W with automatic calibration
2
2
within a range of 0...2000 ppm or 0...5000 ppm, air
2
(continued on next page!)
Rev. 2018 - V27 GB

Advertisement

loading
Need help?

Need help?

Do you have a question about the AERASGARD RCO2-W and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for S+S Regeltechnik AERASGARD RCO2-W

  • Page 1 ® AERASGARD - W ⁄ RLQ - CO - W ⁄ RFTM - LQ - CO - W ⁄ RTM - CO - SD Rev. 2018 - V27 GB The maintenance-free microprocessor-controlled room sensor AERASGARD ® RTM - CO - SD with automatic calibration (fixed) is used for detecting the content of the air within a range of 0...2000 ppm and the temperature within a range of 0...+50°C.
  • Page 2: Technical Data

    ® AERASGARD - W ⁄ RLQ - CO - W ⁄ RFTM - LQ - CO - W ⁄ RTM - CO - SD Rev. 2018 - V27 GB TECHNICAL DATA (continued) Pressure dependence: ± 0.13 % ⁄ mm Hg Long-term stability: <...
  • Page 3 ® AERASGARD - W ⁄ RLQ - CO - W ⁄ RFTM - LQ - CO - W ⁄ RTM - CO - SD Rev. 2018 - V27 GB RTM - CO - SD Schematic diagram RFTM - LQ - CO Schematic diagram Plug for sensor...
  • Page 4 Mounting and Installation ATTENTION!  The minimum CO concentration of outdoor air amounts to approx. 350 ppm (output voltage = 1.75 V at MR = 0...2000 ppm or 0.7 V at MR = 0...5000 ppm) in leafy, hardly industrialised areas. Gas inter-exchange in the sensor element happens by diffusion. Depending on the changes to the concentration and the flow velocity of the air surrounding the sensor, the reaction of the device to the change of concentration may take place with a delay.
  • Page 5 Mounting and Installation Putting in operation After switching on the device, a self-test and tempering period follows. This procedure takes 30 - 50 minutes,depending on the ambient conditions. During this time the output analogue voltage differs from the actual measured value. Switching point setting A potential-free changeover contact is available as a switch output.
  • Page 6: Supply Voltage

    Mounting and Installation SUPPLY VOLTAGE : Connecting scheme Individual operation For operating voltage reverse polarity protection, a one-way rectifier or reverse polarity protection diode is integrated in this device variant. This internal one-way rectifier on AC supply voltage. The output signal is to be tapped by a measuring instrument. The output signal is measured her against zero potential (O V) of the input voltage! Circuitry When this device is operated on DC supply voltage , the operating voltage...
  • Page 7 General notes – This device may only be used in pollutant-free non-precipitating air without above-atmospheric or below-atmospheric pressure at the sensor element. – On outdoor and duct sensors, the sinter filter of the senor element protects the humidity sensor against potential dust exposure. In case of pollution ⁄...