Siemens CP 1243-8 IRC Operating Instructions Manual page 61

Simatic net s7-1200 telecontrol
Table of Contents

Advertisement

Parameter in STEP 7 Basic /
Professional
Password
Partner IP address
Time synchronization: Adoption of parameters from STEP 7 V5
The parameter group "Time synchronization" is only displayed after you have imported the
configuration data from the STEP 7-V5 project.
Adoption of parameters from the STEP 7 V5 project
The displayed parameters are shown alongside the corresponding parameters in STEP 7
V5.
Parameter in STEP 7 Basic /
Professional
Synchronization cycle
Second intervals
Minute intervals
Hourly intervals
User defined time
No synchronization
Hours / Minutes / Seconds
Time Master
In the text file of the configuration data you will find the parameters in the SDB "WAN data".
Ethernet interface (X1) > Advanced options > TCP connection monitoring
The setting applies to all TCP connections of the CP.
Exception: The settings made here do not apply to connections programmed for Open User
Communication with the program blocks.)
TCP connection monitoring time
If there is no data traffic within the connection monitoring time, the CP sends a keepalive to
the communications partner.
TCP keepalive monitoring time
After sending a keepalive, the CP expects a reply from the communications partner within
the keepalive monitoring time. If the CP does not receive a reply within the configured time,
the keepalive frame is repeated twice. After the monitoring time elapses three times without
a reply, the CP terminates and re-establishes the connection.
CP 1243-8 IRC
Operating Instructions, 06/2015, C79000-G8976-C385-01
Parameter in STEP 7 V5
Password
Parameter in STEP 7 V5
Synchronization cycle
Second scheme
Minute scheme
Hour scheme
Time of day
No synchronization
Hour scheme / Minute
scheme / Second scheme
Synchronization master
4.7 Configuration in STEP 7 Basic
Configuration in STEP 7 V5
SINAUT configuration tool >
"MSC Station Properties"
SINAUT configuration tool >
"MSC Master Properties"
Configuration in STEP 7 V5
Properties dialog TIM >
"Time Service" tab
Properties dialog TIM >
"Time Service" tab
Properties dialog TIM >
"Time Service" tab
Properties dialog TIM >
"Time Service" tab
Configuration and operation
Remarks
IP address of the router
(Internet Access)
Remarks
Displays the configured
value
61

Advertisement

Table of Contents
loading

Table of Contents