(a) 2-wire type
DIP switch (RC AD SW)...Factory setting "00"
Since the remote controller address settings are automatically confi gured, you do not
need to confi gure them.
If confi guring manually, it is necessary to confi gure both the indoor unit and the remote
controller. For details, please refer to the remote controller installation manual.
(b) 3-wire type
DIP switch (RC AD SW)...Factory setting "00"
When connecting multiple indoor units to 1 standard wired remote controller, set the
address at RC AD SW in sequence from "00".
Setting
Setting range
Remote controller
00 to 15
address
Example
If 4 indoor units are connected.
Indoor unit 1
Indoor unit 2
RC AD SW
RC AD SW
00
01
Remote
controller
Set the R.C. address in accordance with the table below.
Indoor unit
R.C. address
1
1
00
OFF
2
01
ON
3
02
OFF
4
03
ON
5
04
OFF
6
05
ON
7
06
OFF
8
07
ON
9
08
OFF
10
09
ON
11
10
OFF
12
11
ON
13
12
OFF
14
13
ON
15
14
OFF
16
15
ON
NOTES:
Be sure to set consecutive R.C. address.
The indoor units cannot be operated if a number is skipped.

6. 2. Multiple remote control

Up to 2 remote controllers can be used to operate the indoor units.
Multiple installation method described above is prohibited to combine 3 Wired type
with 2 Wired Type.
I.U.
A
Master
A, B : Remote controller cable. (Refer to 2. 4. Electrical requirement.)
A ≤ 500 m, A+B ≤ 500 m
Switch 100
ON
Setting
example 00
1
2
3
4
RC AD
Indoor unit 3
Indoor unit 4
RC AD SW
RC AD SW
03
02
DIP SWITCH No.
2
3
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
OFF
OFF
ON
OFF
OFF
ON
ON
OFF
ON
ON
OFF
ON
OFF
ON
ON
OFF
ON
ON
ON
ON
ON
ON
ON
ON
CAUTION
I.U.
A
B
Master Slave

7. FUNCTION SETTING

Refer to the installation manual of remote controller for setting method.

7. 1. Function Details

■ Filter sign
Select appropriate intervals for displaying the fi lter sign on the indoor unit according to the
estimated amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Function
Setting
number
11
■ Ceiling height
Select the appropriate ceiling height according to the place of installation.
Function
Setting
number
20
4
The ceiling height values are for the 4-way outlet.
Do not change this setting in the 3-way outlet mode.
■ Outlet directions
Select the appropriate number of outlet directions according to the installation conditions.
Function
Setting
number
22
■ Vertical wind direction adjustment range
To prevent draft, change the setting to "Upward" (01).
Note that the airfl ow in certain usage conditions may leave the ceiling dirty. In such cases,
the use of the optional "PANEL SPACER KIT" is recommended.
Function
Setting
number
23
Standard
Upward
(♦... Factory setting)
Setting description
value
00
Standard (2500 hours)
01
Long interval (4400 hours)
02
Short interval (1250 hours)
03
No indication
(♦... Factory setting)
Setting description
value
Standard (3.0 m : 18/24 type)
00
(3.2 m : 30/36/45/54 type)
High ceiling (3.5 m : 18/24 type)
01
(4.2 m : 30/36/45/54 type)
02
Low ceiling (2.7 m)
(♦... Factory setting)
Setting description
value
00
4-way
01
3-way
(♦... Factory setting)
Setting description
value
00
Standard
01
Upward
Ceiling
UP
Swing range
Outlet cross section
En-13