EP03-300-200
Release 200
Table 5. Honeywell-Recommended ControlNet Coaxial Trunk Cable Types (cont'd)
Notes:
1.
ControlNet is a registered trademark of ControlNet International, Ltd.
2.
Meets electrical/mechanical requirements of standard trunk cable 51192416
3.
Other jacket colors (white, red, blue, green, orange, brown, yellow, violet, or gray) available if specially ordered
4.
Standard raw trunk cable used in Honeywell-supplied, pre-assembled trunk cable assemblies TC-KCCX01 through TC-KCC500
5.
Electrical characteristics are the same as standard ControlNet trunk cable 51192416
6.
Electrical characteristics are the same as standard ControlNet trunk cable 51192416 except greater attenuation results in less
distance capability than 51192416 cable
7.
Standard ControlNet trunk cable connector 51192417-100 is Amphenol part # 31-71000-RFX used in Honeywell-supplied pre-
assembled trunk cable assemblies TC-KCCX01 through TC-KCC500
8.
Connector specified in note 7 above should be usable because cable diameter and jacket thickness dimensions are the same
as (or very close to) standard 51192416 cable
9.
Connector specified in note 7 above may not be usable because cable diameter and jacket thickness dimensions are smaller
than standard 51192416 cable
10. Cables with PE (polyethylene) jacket last longer outdoors than cables with PVC jacket. Protect PVC cables outdoors by
placing them in conduit away from moisture.
11. This cable is also available with PE jacket
12. All cables in the table above are 75-ohm, RG6/U-style, quad-shield (foil/braid/foil/braid) cables with suitable electrical
characteristics for ControlNet networks
13. Belden states this armored cable can be used outdoors (without conduit protection) but not for direct burial. Basically it is
Belden 3092A cable with armoring and outer PVC jacket.
14. Belden states this armored cable can be used outdoors (without conduit protection) and also for direct burial (due to moisture
immunity of jacket and underlying tape). Basically it is Belden 3092A cable with armoring, flooding, and outer PE jacket.
15. Refer to supplier's datasheet for approval information printed on cable jacket, especially for approvals needed for Canadian
applications
16. CommScope states that the armor is also available in interlocked aluminum or steel