Specifications And Sizing; Controller Environmental And Compliance Certifications - Honeywell Experion PKS Specifications And Technical Data

Cee-based controller
Hide thumbs Also See for Experion PKS:
Table of Contents

Advertisement

EP03-300-200
Release 200

Specifications and Sizing

Controller Environmental and Compliance Certifications

The Experion PKS C200 Controller and I/O Modules meet the following certifications:
Table 1. C200 Controller & I/O General Environmental and Agency Certifications
Parameter
Environmental Conditions
Operating Temperature
Storage Temperature
2
Relative Humidity
Temp. Rate of Change
Uncoated Models (TC-xxxxxx)
Coated Models (TK-xxxxxx)
Vibration (3 axes)
Frequency
Acceleration
Displacement
Mechanical Shock
Acceleration
Duration
Barometric Pressure
Altitude
Agency Certification
(when product is marked)
Removal/Insertion Under Power
(RIUP)
1
The above environmental and agency specifications apply to all Experion PKS Chassis Series A models,
including Controllers, Power Supplies and I/O, except where noted.
The maximum relative humidity specification applies up to 40 ° C. Above 40 ° C the RH specification is de-
2
rated to 55% to maintain constant moisture content.
3
With an enclosure.
Experion PKS CEE-based Controller Specifications and Models
0 to 60 °C (32 to 140°F)
-40 to 85°C (-40 to 185°F)
5 to 95% non-condensing
≤ 1°C/min. (≤ 5°C/min. storage)
Mild (G1)
3
Moderate (G2) or Harsh (G3)
Operative and Storage Limits
10 to 60 Hz
0.5 g max.
0.1 inches
5 g max.
30 ms max.
-300 to +3000 m
(C-Tick)
PERMITTED when equipment is installed in ordinary, non-
hazardous, locations (I/O modules reload automatically).
Not permitted when equipment is installed in a Class I, Division 2,
Hazardous (Classified) Location.
15
December, 2003
Specification
Transportation Band
10 to 60 Hz
1 g max.
0.1 inches
20 g max.
30 ms max.
Any
UL 508 Industrial Control Equipment
Class I, Div 2, Groups A, B, C & D
Hazardous and Ordinary locations
(Maintenance may require a hot work
permit)
89/336/EEC, EMC Directive
EN 50081-2, Emissions, Industrial
EN 50082-2, Immunity, Industrial
Meets requirements of the Australian
Radiocommunications Act of 1992,
Section 182, relating to electromagnetic
compatibility.