Operation - Honeywell Modutrol IV M6284A1089-S Product Data

Table of Contents

Advertisement

Available languages

Available languages

SERIES 61 AND SERIES 62 MODUTROL IV™ MOTORS
MOVE SCREWDRIVER AT
TOP ONLY TO ADJUST CAM.
1/8 INCH
STRAIGHT-BLADE
SCREWDRIVER
SLOW RISE
PORTION
(APPROX.
10 DIFF.)
LEFT/OUTER
AUXILIARY
SWITCH
FAST RISE
PORTION
(APPROX.
1 DIFF.)
MOTOR
OPEN

OPERATION

Use Series 61 and 62 Modutrol IV Motors for standard Series
60 operation (drive open, hold, drive closed). Series 62
motors can also be used with the feedback potentiometer as
an input to the controller.
See Table 10 for details on motor response to controller
signals.
NOTE: Reverse the wires at either the motor or control-
ler.
To reverse the rotation direction of a non-spring return motor:
• Reverse the wires at terminals W and B.
Table 10. Modutrol IV Motor Operation.
Terminal Connection
Motor Type
Series 61 Series 62
Non-Spring Return
R-W
or Spring Return
R-B
Non-Spring Return
R-nothing
or Spring Return
Non-Spring Return Power
Failure
Spring Return
Only Upon
Power
Failure
63-2629EF—01
NOTE: CAMS ARE OFFSET VERTICALLY TO
RIGHT/INNER
AUXILIARY
SWITCH
INNER
AUXILIARY
CAM
(BLUE)
FAST RISE
PORTION
(APPROX.
1 DIFF.)
SLOW RISE
PORTION
(APPROX.
OUTER
10 DIFF.)
AUXILIARY
CAM
(RED)
MOTOR
CLOSE
POWER
END
Fig. 14. Auxiliary switch adjustment.
Resulting
Action
R-1
ccw (closed)
R-2
cw (open)
R-nothing
stops driving
Power
stops (none)
Failure
Only Upon
spring return
Power
(closed)
Failure
PROVIDE BETTER VIEW OF BACK CAM.
LEFT/OUTER
AUXILIARY
SWITCH
POWER END
OF MOTOR
CHECKOUT
After the installation and linkage adjustment, check the entire
motor and control hookup. Proper checkout ensures that:
• The motor operates the load (damper or valve) properly.
• The motor responds properly to the controller as the input
varies. See Table 10.
• The auxiliary switch, if used, operates at the desired point
of motor rotation.
1. Inspect motor, linkage, and valve or damper to ensure
all mechanical connections are correct and secure.
NOTE: In damper installations, the pushrod should not
extend more than a few inches past the ball
joints.
2. Ensure that there is adequate clearance for the linkage
throughout the entire motor stroke without binding or
striking other objects.
3. Drive the motor fully open and fully closed. See Table
10.
NOTE: Refer to controller or system instructions for
additional checkout procedures.
M62 Checkout
The following procedure will verify that the M62 external
feedback potentiometer is working for a -F or -S model.
• Connect 24 VAC to terminals 3 and 4.
• Connect 5-10 VDC to terminals Y and G (connect +
to Y and - to G).
• Connect either a voltmeter or an oscilloscope to
terminals T and G (connect + to T and - to G).
• Connect terminal R to terminal 1 to drive the motor
towards the fully closed position.
12
RIGHT/INNER
AUXILIARY SWITCH
INNER AUXILIARY
CAM (BLUE)
OUTER AUXILIARY
CAM (RED)
M13700

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents