Maintenance - Siemens ACVATIX SAYxP Series Manual

Electromotoric actuators for valves with a 15 mm stroke
Table of Contents

Advertisement

Combinations
Type
VPI46.40F9.5Q
VPI46.50F12Q
Product documentation
Notes
Engineering
SAY31P03 and
SAY81P03
SAY61P03
Mounting
Mounting positions
Acting direction

Maintenance

Siemens
Building Technologies
Stock no.
DN
40
S55264-V129
50
S55264-V130
Detailed Informations about the New Generation actuators can be found in the Basic
documentation for actuators (P4040).
3-position actuators must have their own specific controller, refer to "Connection
Diagrams" (page 8).
Up to 10 actuators can drive in parallel on a controller output with a rating of 1 mA.
Modulating actuators have an input impedance of 100 kΩ.
Indoor use
With valves whose stem is retracted in the fully closed position, "direct acting" means
that the valve is fully closed (100 %) when positioning signal Y = 0 V and Z = 0 Ω re-
spectively.
Y, Z
Positioning signal
V
Volumetric flow
Acting direction: direct
The actuators are maintenance-free.
Electromotoric actuators for valves
V %
V %
∆p
H
min
100
min
100
[mm]
[l/h]
[l/h]
[kPa]
1370
9500
25
15
1400
11500
36
1)
Only in connection with weather shield ASK39.1
Direct acting
Pos. signal Y
DC 0...10 V
4...20 mA
Pos. signal Z
0...1000 Ω
Data sheet
N4855
1)
Outdoor use
A6V10628469_de--_c
2018-03-12
3 / 10

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acvatix say31p03Acvatix say61p03Acvatix say81p03

Table of Contents