Speci cations
52
S&C Instruction Sheet 659-540
The PureWave SMS-250 system is capable of servicing the distributedpower genera-
tion needs of its users when operated within its design limitations and specifications.
Nonproprietary operation specifications for the PureWave SMS-250 system beyond
those identified in this instruction sheet may be obtained from S&C Electric Company.
Table 10. System Specifications
Description
Real/Reactive Power
Secondary Voltage
Frequency
Dimensions (single enclosure)
Weight
Table 11. Environmental Specifications
Description
Ambient Operating
Temperature
Storage Ambient Temperature
Humidity
Altitude
Seismic
Audible Noise
NOTICE
Value or Range
263 kW/263 kVA
380 Vac directly
400, 415, or 480 Vac using an auto transformer
50 or 60 Hz
36 W × 36 L × 80 H inches
(914 × 914 × 2032 mm)
2,000 lbs (907.2 kg)
Value or Range
-40°F to 104°F (-40°C to 40°C) without de-rating
-49°F to 140°F (-45°C to 60°C)
0% to 100% condensing
Sea level to 1,000 meters without de-rating
Uniform Building Code Zone 4
< 55 dBA at 3 meters when inverter is not running;
< 65 dBA at 3 meters when inverter is running
Need help?
Do you have a question about the PureWave SMS-250 and is the answer not in the manual?