Technical data (cont'd)
Cross-sectional areas
Building Technologies Division
Industry Sector
Individual contact loading:
Fan motor contactor
•
Nominal voltage
•
Nominal current
•
Power factor
Alarm output (nominal voltage)
•
Nominal current
•
Power factor
Ignition transformer (nominal voltage)
•
Nominal current
•
Power factor
Fuel valves-gas (nominal voltage)
•
Nominal current
•
Power factor
Fuel valves-oil (nominal voltage)
•
Nominal current
•
Power factor
Cable lengths
•
Mains line
•
HCFN line
•
Analog line
•
Flame detector
•
CAN bus
Note!
¹) If the cable length exceeds 50 m, additional loads must not be connected to the
status inputs (refer to «Power supply for the LMV5... system»)!
Above a certain cable length, the actuators must be powered by a separate transformer
installed near the actuators.
The cross-sectional areas of the mains power lines (L, N, PE) and, if required, the
safety loop (safety limit thermostat, water shortage, etc.) must be sized for nominal cur-
rents according to the selected external primary fuse. The cross-sectional areas of the
other cables must be sized in accordance with the internal unit fuse (max. 6.3 AT).
Min. cross-sectional area
Cable insulation must meet the relevant temperature requirements and conform to the
environmental conditions. The CAN (bus) cables have been specified by Siemens and
can be ordered as accessory items. Other cables must not be used. If this is not
observed, the EMC characteristics of the LMV5... system will be unpredict-
able!
Fuses used in the LMV5... basic unit
- F1
- F2
- F3
AC 120 V
AC 230 V
1 A
1 A
Cosϕ >0.4
Cosϕ >0.4
1 A
1 A
Cosϕ >0.4
Cosϕ >0.4
1.6 A
2 A
Cosϕ >0.2
Cosϕ >0.2
1.6 A
2 A
Cosϕ >0.4
Cosϕ >0.4
1.6 A
1 A
Cosϕ >0.4
Cosϕ >0.4
Max. 100 m
Max. 100 m
(100 pF/m)
(100 pF/m)
Max. 100 m
Max. 100 m
(100 pF/m) ¹)
(100 pF/m) ¹)
Max. 100 m
Max. 100 m
(100 pF/m)
(100 pF/m)
Refer to chapter «Technical Data / Flame
supervision»
Total lengths max. 100 m
0.75 mm²
(single- or multi-core to VDE 0100)
6.3 AT
6.3 AT
DIN EN 60127 2/5
DIN EN 60127 2/5
4 AT
4 AT
GMD-4A
DIN EN 60127 2/5
4 AT
4 AT
GMD-4A
DIN EN 60127 2/5
9/39
CC1N7550en
24.05.2011