Liquid Push/Pull Procedure - TOTALINE TTL-RECO250S User Manual

Refrigerant recovery unit
Table of Contents

Advertisement

Available languages

Available languages

 
Push/pull procedure only  works with  large systems  where the  liquid 
refrigerant is no less than 6.8kg (15lbs). 
 
1.      Put MODE valve knob on RECOVER 
  2.      Open OUTPUT valve. 
3.
Open INPUT valve. 
4.
When the scale stops rising close all ports  
5.
Switch off the machine. 
 
CAUTION: 
When using the Push/pull method, a scale must be used to avoid over 
filling the storage tank, once the siphon is started, it can continue and 
overfill the storage  tank even  if the  tank  is equipped with a float 
level sensor. The siphon  can continue even when the machine is 
turned off.  You  must manually  close the valves on the tank and the 
unit to prevent overfilling  of  the recovery tank.
 
LIQUID PUSH/PULL PROCEDURE 
8 EN
 