Mitsubishi Electric RD78G4 User Manual page 79

Motion module
Hide thumbs Also See for RD78G4:
Table of Contents

Advertisement

Error
Error definition and causes
code
CF41H
Incorrect frame was received.
CF42H
Incorrect frame was received.
CF43H
An error has occurred.
CF44H
Incorrect frame was received.
D0A3H
Send processing of the transient
transmission has failed.
D203H
The read data or write address of the
transient transmission is incorrect.
D205H
The target station No. of transient
transmission is incorrect.
D20AH
The target station No. of transient
transmission is incorrect.
D20BH
There was no master station when the
specified master station was specified for
transient transmission.
D20CH
There was no master station when the
current master station was specified for
transient transmission.
D20DH
Transmission completion wait timeout has
occurred in transient data transmission.
D20EH
The header information of transient
transmission is incorrect.
D20FH
In transient transmission, the command
which cannot be requested to all or a
group of stations was executed with all
stations specification or group
specification.
D213H
• The command of transient transmission
is incorrect.
• The CC-Link IE TSN/CC-Link IE Field
diagnostics was used for the network to
which the relay receiving station
belongs.
D214H
The data length of transient transmission is
incorrect.
Action
• Check the operating status and connection status of the target device.
• Check the connection of the Ethernet cable and hub.
• Check the line status of Ethernet.
• Reset the CPU module and target device, and retry the operation.
If the above actions do not solve the problem, contact the manufacturer of the
target device.
• Check the operating status and connection status of the target device.
• Check the connection of the Ethernet cable and hub.
• Check the line status of Ethernet.
• Reset the CPU module and target device, and retry the operation.
If the above actions do not solve the problem, contact the manufacturer of the
target device.
• Check the operating status of the external device.
• Check if there is any error in the line status.
If the above actions do not solve the problem, contact the manufacturer of the
target device.
• Check the operating status and connection status of the target device.
• Check the connection of the Ethernet cable and hub.
• Check the line status of Ethernet.
• Reset the CPU module and target device, and retry the operation.
If the above actions do not solve the problem, contact the manufacturer of the
target device.
• Check the network status using the CC-Link IE TSN/CC-Link IE Field
diagnostics of the engineering tool, and take action.
• When the own station, target station, or relay station detected an error,
identify the cause of the error and take action.
• Correct the target station No. of transient data, and retry the operation.
• When the access destination is a module with a different network No.,
check if "Routing Setting" of "CPU Parameter" is correctly set.
Correct the read data or write address at the transient request source, and
retry the operation.
Correct the target station No. at the transient request source, and retry the
operation.
Correct the target station No. at the transient request source, and retry the
operation.
Correct the target station No. at the transient request source, and retry the
operation.
Correct the target station No. at the transient request source, and retry the
operation.
• Check the network status using the CC-Link IE TSN/CC-Link IE Field
diagnostics of the engineering tool, and take action.
• When the own station, target station, or relay station detected an error,
identify the cause of the error and take action.
• Lower the transient transmission usage frequency, and retry the operation.
• Check if the switching hub and the cables at the request source are
connected properly.
Correct the header information at the transient request source, and retry the
operation.
Check that the command can be requested to all or a group of stations at the
transient request source, and retry the operation.
• Correct the request command at the transient request source, and retry the
operation.
• Review the connection destination so that the CC-Link IE TSN/CC-Link IE
Field diagnostics is used for the network to which the relay sending station
belongs.
Correct the data length at the transient request source, and retry the
operation.
Detailed
information
3 TROUBLESHOOTING
3.5 List of Error Codes
3
77

Advertisement

Table of Contents
loading

Table of Contents