N05010/N10010 DAMPER ACTUATORS FOR MODULATING AND FLOATING/2-POSITION CONTROL

PRODUCT IDENTIFICATION SYSTEM

N = non-spring return
S = spring return
05 = 5
10 = 10 Nm
SmartAct
N 0 5 0
010 = modulating + floating
24 = 24 V floating + ON/OFF
230 = 230 V ON/OFF
Fig. 1. Product Identification System
MODELS
order no.
supply voltage
N05010
N05010-SW2
24 Vac/dc
N10010
N10010-SW2

BASIC FEATURES

1
2
N05010
3
4
5
6
Fig. 2. Setting units and control elements
Legend for Fig. 2:
1) Universal shaft adapter
2) Mechanical end limits
3) Declutch button
4) Function selection switch
5) Removable access cover
6) Anti-rotation bracket
EN0B-0478GE51 R0105
Nm
equipped with two
end switches
1
0
-
S
W 2
+ ON/OFF
end switches
torque
--
5 Nm
2
--
10 Nm
2
2...10 V
0...10 V
Dir
Service/Off
Rev
10...0 V
10...2 V
Contents of Package
The delivery package includes the actuator, parts 1 through 6
(see Fig. 2), plus two cable grommets and a spare cable
grommet.

RUN MODES

The function selection switch (see Fig. 3) can be used to
place the actuator into any one of three different modes:
Service/Off;
the floating/2-position run mode ("Dir" for CCW-closing
dampers or "Rev" for CW-closing dampers); and
the modulating run mode.
modulating
2...10 V
0...10 V
Dir
Service/Off
Rev
10...0 V
10...2 V
Fig. 3. Function selection switch
Power-Off Behavior
If power is removed, the shaft adapter remains in position.
Service/Off
If the function selection switch is set to the "Service/Off"
position, then all rotary movement is cancelled, and all control
signals are ignored, thus allowing the actuator to be manually
operated safely.
Floating/2-Position Run Mode
Without Feedback Signal
If, however, the function selection switch has been set to one
of the two floating/2-position control settings – but the
actuator has not been wired for a feedback signal (see Fig. 12
and Fig. 13) – then as soon as operating power is applied, the
shaft adapter will run according to the control signals applied.
With Feedback Signal
If the function selection switch has been set to one of the two
floating/2-position control settings – and if the actuator has
been wired for a feedback signal (see Fig. 12 and Fig. 13) –
then as soon as operating power is applied, the shaft adapter
will likewise run first completely counterclockwise and then
completely clockwise (see also section "Adaption"), after
which it will run according to the control signals applied.
Modulating Run Mode
If the function selection switch has been set to one of the four
modulating control settings – and if the actuator is wired
correspondingly (see Fig. 11) – then as soon as operating
power is applied, the shaft adapter will run first completely
counterclockwise and then completely clockwise (see also
section "Adaption"), after which it will run according to the
control signals applied.
2
floating/2-position
Service/Off
2...10 V
0...10 V
Dir
Service/Off
Rev
10...0 V
10...2 V
2...10 V
0...10 V
Dir
Service/Off
Rev
10...0 V
10...2 V