Fit the probe where it is not accessible by the End User. The instrument must not be opened. • In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.p.a.” (see • address) with a detailed description of the fault.
NOTE: the set value is stored even when the procedure is exited by waiting the time-out to expire. 3.2 HOW TO SET THE RANGE OF THE PRESSURE PROBES If a instrument with the following part number is used: XC642C – xxxxF, it is pre-set to work with pressure probe with the following range:...
To lock and unlock the keyboard. n n n n SET + To enter the programming mode. o o o o SET + To exit the programming mode. 1592001330 XC642C GB r1.0 07.06.2004.doc rel. 1.0 Pa. 5 / 21...
To memorise the new value and pass to the fan set point push the SET key. To change its value push the o o or n n within 30s. To exit: push the SET key or wait for 30 without pressing any keys. 1592001330 XC642C GB r1.0 07.06.2004.doc rel. 1.0 Pa. 6 / 21...
“oFF” label if the output is disabled for a maintenance section. With compressor with more steps all the LED’s linked to the compressor and the valves are switched on.. Select the output by pressing the UP or DOWN key. 1592001330 XC642C GB r1.0 07.06.2004.doc rel. 1.0 Pa. 7 / 21...
To see the alarm duration and push the SET key. o o o o or SET By pushing again the key the next alarm is displayed. Alarms erasing. Enter the Alarm Menu. 1592001330 XC642C GB r1.0 07.06.2004.doc rel. 1.0 Pa. 8 / 21...
HACCP menu. 11.2 TO UNLOCK THE KEYBOARD Keep the o o and n n keys pressed together for more than 3s till the “POn” flashing message appears. 1592001330 XC642C GB r1.0 07.06.2004.doc rel. 1.0 Pa. 9 / 21...
CL: the digital input is activated by closing the contact. Configurable digital input polarity functions (terminals 3 - 4) 1592001330 XC642C GB r1.0 07.06.2004.doc rel. 1.0 Pa. 10 / 21...
(possibly after the tAo delay time). tAo: Low and High pressure (temperature) alarms delay– compressor section: (0÷255 min) time interval between the detection of a pressure (temperature) alarm condition and alarm signalling. 1592001330 XC642C GB r1.0 07.06.2004.doc rel. 1.0 Pa. 11 / 21...
Relay valve 1 (66%) 100% Pression Compressor at 100% Set + (Pbd/2) Neutral Zone Time Set - (Pbd/2) Loads state Compressor disabled oA1(Compressor) On oA2(33%) On oA3(66%) Delay evolution Time Time 1592001330 XC642C GB r1.0 07.06.2004.doc rel. 1.0 Pa. 13 / 21...
Keep the probe and the digital input wires separate from the power cable. Do not exceed the maximum rating current for each relay, check technical data and if the load is bigger, use filtered contactors. 1592001330 XC642C GB r1.0 07.06.2004.doc rel. 1.0 Pa. 15 / 21...
Second probe presence. dSEP Dynamic set point enabling Probe for analog output Probe for triac output When these parameters are set in wrong way an alarm message is generated: 1592001330 XC642C GB r1.0 07.06.2004.doc rel. 1.0 Pa. 16 / 21...
Page 17
(E.I. for lack of oil or overheating, etc,) the corresponding load is turn off. Parameters ALIP: It establishes if the input is activated by closing (ALIP=cL) or by opening (ALIP=oP) the terminals. 1592001330 XC642C GB r1.0 07.06.2004.doc rel. 1.0 Pa. 17 / 21...
When the input is disable: unchanged. hold pressed the Restart(DOWN)key for 3s or turn off and on the instrument.. The compressors restarts working according to the working algorithm. 1592001330 XC642C GB r1.0 07.06.2004.doc rel. 1.0 Pa. 18 / 21...
Page 19
A load has worked - signalling only Manually: reset the running hour of the compressor maintenance for the hour set in (see par.8 Running hours of loads) alarm the SEr parameter 1592001330 XC642C GB r1.0 07.06.2004.doc rel. 1.0 Pa. 19 / 21...
Need help?
Do you have a question about the XC642C and is the answer not in the manual?
Questions and answers