Table 2-5. Typical Power Usage – Standard Power Mode at room temperature
Description
Base flow computer with integral multivariable DP and
pressure sensor and temperature measurement for a single
meter run
Base flow computer with temperature measurement (no
integral sensor) communicating to remote 4088B (externally
powered) for a single meter run
Base flow computer with integral multivariable DP and
pressure sensor and temperature measurement, 2 digital and
2 analog channels available for a single meter run
Base flow computer with temperature measurement, integral
static pressure sensor and pulsed input for a single meter run
Base flow computer with integral multivariable DP and
pressure sensor and temperature measurement,
communicating to remote 4088B (externally powered) for a
dual meter run
Additional Load Options:
Display and backlight active
FBxWifi active
FBxWifi and display active
DO active (1 Hz, 50:50 duty cycle, no load)
PI active (10 KHz, 50:50 duty cycle, square wave)
8-channel expansion I/O module installed (isolated)
Additional 6-channel expansion I/O module installed
(isolated)
Ethernet enabled 100 Mbit
Ethernet active 100 Mbit
Loop power supply

Notes on Battery Life

Battery life varies based on numerous factors including temperature, communication usage, and
various load options. To achieve the maximum battery life noted in the product data sheet requires
that you:
34
Limit use of the display, backlight, and FBxWifi options.
Power Usage
Power Usage
(mW) at 12Vdc
(mW) at 24Vdc
240
290
220
268
260
313
276
330
250
300
159
188
191
199
233
245
20
23
14
15
228
280
68
66
430
466
640
650
310
393