Honeywell Modutrol IV Series 61 Manual page 3

Hide thumbs Also See for Modutrol IV Series 61:
Table of Contents

Advertisement

1/4
(7)
5
4-1/16 (103)
1-1/2 (37)
1
AUXILARY
END
9/16 (15)
ADAPTER
BRACKET
Fig. 1. Series 61 and 62 Modutrol IV Motor mounting dimensions in in. (mm).
Electrical Ratings: See Table 2.
Table 2. Series 61 and 62 Modutrol IV Motor
Power Consumption Ratings.
Internal
Voltage at
Transformer
50/60 Hz
No
24
Yes
24
120
208
240
TOP VIEW
13/16
(20)
3
4-1/16 (103)
1-1/2 (37)
4
4-1/16 (103)
POWER
END
2
Power Consumption
Non-Spring
Spring
Return
Return
(VA)
(W)
(VA)
17
15
21
26
20
30
26
20
30
26
20
30
27
20
34
SERIES 61 AND SERIES 62 MODUTROL IV™ MOTORS
TOP VIEW OF BRACKET
4-7/8
(124)
4-5/8
(116)
5-1/2
(140)
WIRING
BOX
3/4
(19)
MOTOR
6-7/16
(164)
SPRING RETURN MODEL SHOWN
5-3/8
1
SOME MODELS DO NOT HAVE AN AUXILIARY
(137)
SHAFT. ALL OTHER DIMENSIONS ARE THE SAME.
2-9/16
2
FOR HIGH TORQUE (60 LB-IN.) SPRING RETURN
(66)
MODELS 8-3/4 (222); FOR LOW TORQUE (25 LB-IN.)
SPRING RETURN MODELS 8-1/4 (210);
NON-SPRING RETURN MODELS 7-5/16 (185).
FOR HIGH TORQUE (60 LB-IN.) SPRING
3
RETURN MODELS (SHOWN).
4
FOR LOW TORQUE (25 LB-IN.) SPRING
RETURN MODELS.
3/4
(19)
5
FOR NON-SPRING RETURN MODELS.
Auxiliary Switch Ratings: See Table 3.
Single Contact
Rating
Full Load
Locked Rotor
(W)
a
40 VA pilot duty, 120/240 Vac on opposite contact.
20
25
Control Inputs:
Floating three-wire (Series 60): drive open, hold, drive closed.
25
Series 62 models include an internal, electrically isolated
25
feedback potentiometer that provides shaft position
indication.
25
3
11/16
POWER END
1/4 (7)
4-7/8 (124)
5-9/16 (141)
Table 3. Auxiliary Switch Ratings.
a
120V (in Amps)
7.2
43.2
4-1/4
(107)
5-13/16
(148)
2-5/16
(58)
(17)
M17089BB
240V (in Amps)
3.6
21.6
63-2188—4

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Modutrol iv series 62

Table of Contents