Mitsubishi Electric Lossnay VL-220CZGV-EB Handbook page 23

Hide thumbs Also See for Lossnay VL-220CZGV-EB:
Table of Contents

Advertisement

2 Interlocking with external devices
No.
Problem
1 Lossnay interlock
settings cannot be
performed with the
remote controller.
2 Lossnay does not
perform interlock
operation.
Factor
The power of the Lossnay unit is
not ON.
Faulty connection of the remote
controller transmission cable
The power of the Lossnay unit is
not ON.
Faulty connection of the remote
controller transmission cable or
external input/output signal cables
The Lossnay unit is not set for
interlock operation.
The terminal block connected and
the type of external signal do not
match (charged or volt-free)
The type of external signal and
input setting do not match (level
signal or pulse signal).
The Lossnay unit is set to the
delay operation.
The interlock mode of the Lossnay
unit is set to "ON Interlock" or
"OFF Interlock".
When using two Lossnay units,
no Lossnay unit is set to the main
Lossnay.
When using two Lossnay units,
external control signal is input to a
Lossnay unit other than the main
Lossnay.
The Lossnay unit is operating in
the protective mode (intermittent
operation).
Check the items described in (1) 1.
Check the items described in (1) 2.
Check the items described in (1) 1.
Check the items described in (1) 2.
Set the interlock setting.
Check the type of external signal and the con-
nections of the external control input terminal
(TM2).
Check the type of external signal and the setting
of the input (level or pulse).
(See the Lossnay technical manual.)
When PZ-61DR-E is used, it displays the icon
" " that indicates the delay operation is in-
progress.
LED1 (green) on the control circuit board lights.
The Lossnay unit starts operation in 30 minutes
(or 15 minutes) after starting operation by the
external signal.
Check the function selection switch (SW5-1) on
the circuit board or the function setting (No. 9) of
PZ-61DR-E. (See the Lossnay technical manual.)
Check the interlock mode setting.
(See the Lossnay technical manual.)
When using two Lossnay units, set one Lossnay
unit as the main Lossnay (SW5-10 ON) to input
external control signal.
(See the Lossnay technical manual.)
For details, see the Lossnay technical manual.
─ 23 ─