Download Print this page

Honeywell V4055F Product Data page 6

Fluid power actuator with manual control
Hide thumbs

Advertisement

V4055F,G FLUID POWER ACTUATOR WITH MANUAL CONTROL
d. If the inside surfaces are clear of hydraulic fluid,
clean the bonnet assembly and be sure to remove all
hydraulic fluid from the inside and outside of the
actuator mounting curb. This is the "cup-like" area
around the valve stem. Avoid using a cleaning solu-
tion as it may damage the rubber seals used in the
valve.
7. If the valve bonnet assembly is in good condition and is
not replaced, replace the bonnet seal. Do not reuse the
old bonnet seal. See Table 4 below for the seal number.
8. Coat seals with grease provided and position in valve
body/bonnet assembly.
9. Carefully seat the bonnet assembly on the valve body.
Be sure the seals are in their proper position. On those
valves with a spring below the disc, be sure the spring is
centered in the indentation on the inside of the valve
body.
10. After positioning the bonnet assembly, replace the
screws removed earlier.
NOTE: When replacing the bonnet assembly on the 4-
inch valve, draw it evenly into the valve body.
Finger-tighten the eight bolts. Draw the bonnet
assembly into the valve by tightening, in order,
bolts 1, 5, 7 and 3 (two turns each). Repeat until
the bonnet assembly is seated. Tighten the
remaining bolts. Torque the bolts as
follows:
Valve Size
3/4 in. (19 mm) to 1-1/2 in. (38 mm)
2 in. (51 mm) to 4 in. (102 mm)
11. Remount the actuator on the bonnet assembly. Tighten
the two set screws (50-60 inch pounds.
12. Replace the damper crank arm assembly.
13. Re-attach the wires removed from the actuator terminals
and turn on the electrical power.
14. With the gas still off, cycle the actuator to check for
proper mechanical operation.
CAUTION
Be sure to perform a bonnet seal and seat leak
check after installation.
Be sure to read and follow all instructions that come
with the actuators, valves, seal and bonnet kits.
65-0029—01
Replacing The Ready To Open Light (Red)
1. Disconnect power.
2. Pop out light with screwdriver.
3. Connect wires to new light and push light into hole.
Replacement
133398AA
133417AA
136911AA
133398BA
133417BA
136911BA
133398CA
133417CA
136911CA
136308AA
136307AA
136308BA
136307BA
Each replacement assembly contains the bonnet assembly,
Torque
two rubber seals, and a tube of grease. It must be used only on
55 in.-lb.
the type of valve indicated above.
75 in.-lb.
Replacement Seal
133393A
133392A
137253A
Replacing the Ready to Open Light (Red)
1. Disconnect power.
2. Pop out light with screwdriver.
3. Connect wires to new light and push light into hole.
6
Table 3. Replacement Bonnets for
V5055/V5097 Gas Valves.
Bonnet
Valve
V5055A
V5097A
(On-Off)
V5055B
V5097B
(Characterized Guide)
V5055C
V5097C
(Proof of Closure)
V5055D
V5097D
V5055E
V5097E
Table 4. Gas Valve Replacement Seals.
Assy #
Valve Size (in in.)
3/4, 1, 1-1/4, 1-1/2
2, 2-1/2, 3
4
Valve Size (in in.)
3/4, 1, 1-1/4, 1-1/2
2, 2-1/2, 3
4
3/4, 1, 1-1/4, 1-1/2
2, 2-1/2, 3
4
3/4, 1, 1-1/4, 1-1/2
2, 2-1/2, 3
4
3/4, 1, 1-1/4, 1-1/2
2, 2-1/2, 3
3/4, 1, 1-1/4, 1-1/2
2, 2-1/2, 3

Advertisement

loading

  Related Manuals for Honeywell V4055F

This manual is also suitable for: