Removing Faults/Warnings - Beckhoff AX2000 Assembly, Installation, Setup

Digital servo amplifier
Hide thumbs Also See for AX2000:
Table of Contents

Advertisement

Appendix
7.2

Removing faults/warnings

The table below should be regarded as a "First-aid" box. Depending on the conditions in your instal -
lation, there may be a wide variety of reasons for the fault. In multi-axis systems there may be fur-
ther hidden causes of a fault. Our customer service can give you further assistance with problems.
Fault
HMI message:
communication
fault
F01 message:
heat sink
temperature
F02 message:
overvoltage
F04 message:
feedback unit
F05 message:
undervoltage
F06 message:
motor tempera-
ture
F07 message:
aux. voltage
F08 message:
motor runs away
(overspeed)
F11 message:
brake
F13 message:
internal tempera-
ture
F14 message:
output stage
fault
92
02/06
possible causes
— wrong cable used
— cable plugged into wrong position
in servo amplifier or PC
— wrong PC interface selected
— permissible heat sink temperature
exceeded
— regen power is insufficient. Regen
power limit was reached and the
regen resistor was switched off. This
causes excessive voltage in the DC
bus link circuit.
— supply voltage too high
— feedback connector not properly
inserted
— feedback cable is broken, crushed or
otherwise damaged
— supply voltage not present or too low
when servo amplifier is enabled
— motor thermostat has been activated
— feedback connector is loose or break
in feedback cable
— the aux. voltage produced by the
servo amplifier is incorrect
— motor phases swapped
— feedback set up incorrectly
— short-circuit in the supply cable for
the motor-holding brake
— motor-holding brake is faulty
— fault in brake cable
— no brake connected, although the
brake parameter is set to "WITH"
— permissible internal temperature
exceeded
— motor cable has short-circuit/ground
short
— motor has short-circuit / ground short
— output module is overheated
— output stage is faulty
— short-circuit / short to ground in the
external regen resistor
Measures to remove the cause of
the fault
— use null-modem cable
— plug cable into the correct
sockets on the servo amplifier
and PC
— select correct interface
— improve ventilation
— shorten the braking time RAMP
or use an external regen
resistor with a higher power
rating and adjust the regen
power parameter
— use mains transformer
— check connector
— check cable
— only enable the servo amplifier
when the mains supply voltage
has been switched on
delay > 500 ms
— wait until motor has cooled
down, then check why it
became so hot
— tighten connector or use
new feedback cable
— return the servo amplifier to the
manufacturer for repair
— correct motor phase sequence
— set up correct offset angle
— remove short-circuit
— replace motor
— check shielding of brake cable
— brake parameter set to
"WITHOUT"
— improve ventilation
— replace cable
— replace motor
— improve ventilation
— return the servo amplifier to the
manufacturer for repair
— remove short-circuit / ground
short
AX2000 Installation manual