Profisafe Address Types - Siemens SIMATIC S7-1200 Safety Programming Manualline

Hide thumbs Also See for SIMATIC S7-1200:
Table of Contents

Advertisement

2 Configuring Fail-Safe Controllers
2.2

PROFIsafe address types

The PROFIsafe address is used to uniquely address F-I/O and protect standard
addressing mechanisms such as IP addresses. Uniqueness is defined differently
for F-I/O of PROFIsafe address type 1 and F-I/O of PROFIsafe address type 2.
Table 2-1: Differences between the PROFIsafe address types
PROFIsafe address type 1
The uniqueness of the PROFIsafe
address is ensured only by the F-
destination address.
The F-destination address must be
unique throughout the network and the
CPU.
In the safety summary, each F-
destination address has to be checked
for network- and CPU-wide uniqueness
by making sure that the F-destination
address ranges of all F-CPUs do not
overlap.
The F-destination address and the F-
source address are included in the
safety program's CRC.
You must ensure that each PROFIsafe address is unique.
The ever increasing networking of plants and plant sections – especially if
configured separately – makes accurate planning of the PROFIsafe address
assignment all the more necessary.
The use of F-I/O of PROFIsafe address type 2 makes handling PROFIsafe
addresses easier. With mixed configurations or pure address type 1 configurations,
however, one has to be more careful.
Recommendation
Already at the outset of the project, look at possible communication
relationships and network topologies. Consult with the parties involved to
derive measures for assigning PROFIsafe addresses.
Assign separate address ranges to PROFIsafe address types 1 and 2:
Assign a low number range to F-I/O of PROFIsafe address type 1
Assign a high number range to F-I/O of PROFIsafe address type 2.
Always define unique F-source addresses for all F-CPUs. This makes both
working across projects and later extensions easier.
Safety Programming Guideline
Entry ID: 109750255,
V1.0,
10/2017
PROFIsafe address type 2
The uniqueness of the PROFIsafe
address is ensured by combining the F-
source address and the F-destination
address.
The F-destination address must be
unique throughout the CPU and differ
from all other F-destination addresses
of PROFIsafe address type 1 in the
same network.
The F-destination address used for the
F-I/O of an F-CPU must be unique
throughout the network.
The F-destination address and the F-
source address are included in the
safety program's CRC.
1)
.
8