Horizontal Airflow Direction Control; Powerful Operation - Panasonic CS-A7DKD Service Manual

Table of Contents

Advertisement

(Heating Operation condition)
• When the piping air temperature reaches 38°C, the
louver is changed from upper to lower limit. When the
piping air temperature falls to 35°C, the louver is
changed from lower to upper limit.
8.8.2.
Manual Control
• When the vertical airflow direction is set to Manual using the remote control, the automatic airflow is released and the airflow
direction louver move up and down in the range shown in the diagram.
• The louver can be adjusted by pressing the button to the desired louver position.
• When stop operation using the remote control, the discharge vent is reset, and stop at the closing position.
• During Anti-dew condensation prevention, Airflow Direction Manual control angle change from 10°, 15°, 20°, 26°, 32° to 22°,
24°, 26°, 28°, 30° under Cooling and Soft Dry operation mode.
Cooling and Soft Dry Operation
8.9.

Horizontal Airflow Direction Control

• The horizontal airflow direction louvers can be adjusted manually by hand.

8.10. Powerful Operation

• The Powerful operation is to achieve the setting temperature quickly.
(Cooling and Soft Dry Operation condition)
• When Powerful operation is set, the setting temperature will be automatically decreased 3°C internally against the present
setting temperature (Lower temperature limit: 16°C).
• This operation automatically will be running under SHi Fan Speed (Cooling).
• Vertical Airflow Direction:-
- In "Manual" setting, the vane will automatically shift down 10° lower than previous.
- In "Auto" setting, the vane will automatically swing up and down. However the lower limit will be shifted 10° downward.
(Heating Operation condition)
• When Powerful operation is set, the setting temperature will be automatically increased 3°C against the present setting
temperature (Higher temperature: 30°C).
• The Fan Speed will shift as shown below:
CS-A7DKD CU-A7DKD / CS-A9DKD CU-A9DKD / CS-A12DKD CU-A12DKD /
Heating Operation
Heating Operation