Technical data
Mains voltage
Power supply
Operating voltage
Operating current
Battery capacity
Battery monitoring
Network monitoring
Connectable detector series
Number of lines
Loops (with loop extension) or
–
Stubs
–
Number of addresses
Integrated inputs/outputs
Relay output
–
RT alarm
–
RT fault
–
Monitored outputs
–
Alarm
–
Fault
–
Horn
–
Freely programmable inputs/outputs
–
Operating unit
Slots for RS232, RS485 serial ports
Slots for network modules
Slots for loop extension
Mounting spaces for cable kit (communication)
Sounder module
Ethernet port RJ45
Operating temperature
Storage temperature
Air humidity (no condensation permitted)
Dimensions (W x H x D)
Without cover cap
–
With cover cap
–
Color
Housing
–
Cover cap
–
Protection category (IEC 60529)
Approvals
VdS
–
LPCB
–
FM
–
DNV GL (Marine)
–
10
Building Technologies
Fire Safety
AC 115/230 V +10/-15 %
150 W
DC 21...28.4 V
Max. 5 A
2x 12 V, 26 Ah
Yes
Yes
Cerberus PRO FD720 (C-NET)
4 (8)
8 (16)
Max. 504
1
1
1
1
2
12
Integrated
2
2
2
2
Max. 2
1
-8...+42 °C
-20...+60 °C
≤95 % rel.
430 x 796 x 160 mm
430 x 796 x 183 mm
~RAL 7035, light gray
~RAL 000 50 00
IP30
G209077
126bn/07
3051081
See document A6V10339425
A6V10207176_h_en_--
2016-05-23