Haier 1U71S2SG1FA Service Manual page 107

R32 super match ii multi split
Hide thumbs Also See for 1U71S2SG1FA:
Table of Contents

Advertisement

TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFORE MAKING ANY ELECTRIC
CONNECTIONS.
GROUND CONNECTIONS MUST BE COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS.
Precautions for electrical wiring
Electrical wiring work should be conducted only by authorized personnel.
Do not connect more than three wires to the terminal block. Always use round type crimped terminal lugs with
insulated grip on the ends of the wires.
Use copper conductor only.
Selection of size of power supply and interconnecting wires
Select wire sizes and circuit protection from table below. (This table shows 20m length wires with less than 2%
voltage drop.)
Item
Model
AD90S2SM3FA AD90S2SM4FA
AD105S2SM3FA AD105S2SM4FA
AD125S2SM3FA AD125S2SM4FA
AD140S2SM3FA AD140S2SM4FA
POWERSUPPL&YINDOOR-OUTDOORCONNECTION:
Make wiring to supply power to the outdoor unit, so that the power for the indoor unit is supplied by outdoor
unit terminal blocks.
WARNING
DANGER OF BODILY INJURY OR DEATH
Circuit breaker
Switch
Overcurrent
Phase
breaker
protector
(A)
rated capacity (A)
1
40
60
104
Earth leakage breaker
Power source
wire size
Switch
2
(minimum) (mm
)
breaker (A)
6.0
40
Leak
current (mA)
30