Troubleshooting; Testing Wiring Connections; Troubleshooting On The Xcl8010 Controller - Honeywell Excel 800 Installation And Commissioning Instructions

Excel 5000 open system
Table of Contents

Advertisement

Excel 800

Troubleshooting

Testing Wiring Connections

Push-in terminals feature small holes (1 mm in diameter)
which can be used to measure the signals.
Insert a probe (1) as shown on the right.

Troubleshooting on the XCL8010 Controller

The following LEDs of the XCL8010 Controller can be used for troubleshooting purposes:
Power LED (green)
Alarm LED (red)
L
W
service LED
ON
ORKS
C-Bus Tx and Rx LEDs
HMI Tx and Rx LEDs
Modem Interface Tx and Rx LEDs
Power LED (green)
case
Power LED
1
ON
2
Flashing
3
Is extinguished briefly
Table 42 XCL8010 power LED
Meaning
Normal operation
One or more of the internal voltage supplies
are outside of the permissible ranges. The
controller stops operation.
 The operator has activated the reset
button.
 The controller is performing a warm start.
39
Fig. 56
Testing wiring connections
Remedy
No action necessary.
Check power.
Check wiring.
If problem persists, replace hardware.
No action necessary.
Troubleshooting
EN1B-0375GE51 R0315