Troubleshooting
Testing Wiring Connections
Push-in terminals feature small holes (1 mm in diameter)
which can be used to measure the signals.
Insert a probe (1) as shown on the right.
►
Troubleshooting on the XCL8010 Controller
The following LEDs of the XCL8010 Controller can be used for troubleshooting purposes:
Power LED (green)
Alarm LED (red)
L
W
service LED
ON
ORKS
C-Bus Tx and Rx LEDs
HMI Tx and Rx LEDs
Modem Interface Tx and Rx LEDs
Power LED (green)
case
Power LED
1
ON
2
Flashing
3
Is extinguished briefly
Table 42 XCL8010 power LED
Meaning
Normal operation
One or more of the internal voltage supplies
are outside of the permissible ranges. The
controller stops operation.
The operator has activated the reset
button.
The controller is performing a warm start.
39
Fig. 56
Testing wiring connections
Remedy
No action necessary.
Check power.
►
Check wiring.
►
If problem persists, replace hardware.
►
No action necessary.