No. Items
Optional Function
15
C1
Not Prepared
16
C2
Not Prepared
17
C3
Not Prepared
18
C4
Not Prepared
19
C5
Hi Speed
20
C6
Hi Speed at Heating Thermo-OFF
Canceling of Enforced 3 Minutes
21
C7
Minimum Operation Time of
Compressor
22
C8
Thermistor of Remote Control Switch
23
C9
Not Prepared
24
CA
Not Prepared
25
Cb
Selection of Forced Stoppage Logic
26
CC
Not Prepared
27
Cd
Not Prepared
28
CE
Not Prepared
29
CF
Change of Louver Swing Angle
30
d1
Not Prepared
31
d2
Not Prepared
32
d3
Power Supply ON/OFF 2
Prevention for Cooling Discharge Air
33
d4
Temp. Decrease
Prevention for Heating Discharge Air
34
d5
Temp. Decrease
Room Temp. Control for Energy
35
d6
Saving
36
d7
Not Prepared
37
E1
Ventilation Mode
38
E2
Increasing Supply Air Volume
39
E3
Not Prepared
40
E4
Precooling / Preheating Period
41
E5
Not Prepared
Indoor Fan Operation Time After
42
E6
Cooling Operation Stoppage
Individual
Setting
Setting
Condition
00
Not Used
-
01
(Use as 00 conditions)
-
"- -" Fixed Not Used
00
Not Used
01
(Use as 00 conditions)
00
Not Used
01
(Use as 00 conditions)
00
Not Available
01
Hi Speed 1 (*2)
02
Hi Speed 2 (*2)
00
Not Available
01
Available
00
Available
01
Not Available
00
Control by Indoor Suction Thermistor
01
Control by Thermistor of
Remote Control Switch
02
Control by Average Value of
Indoor Suction Thermistor and
Thermistor of Remote Control Switch
-
"- -" Fixed Not Used
-
"- -" Fixed Not Used
00
Forced Stoppage Input: A Contact
X
01
Forced Stoppage Input: B Contact
00
Not Used
X
01
(Use as 00 conditions)
00
Not Used
01
(Use as 00 conditions)
00
Not Used
-
01
(Use as 00 conditions)
00
Standard (7 Steps)
01
Draft Prevention (5 Steps)
02
High Ceiling (5 Steps) (*3)
00
Not Used
01
(Use as 00 conditions)
-
"- -" Fixed Not Used
00
Not Available
01
Available
00
Not Available
01
Available
00
Not Available
01
Available
00
Not Available
01
Available
00
01
02
03
Not Used(Use as 00 conditions)
04
05
06
07
00
Automatic Ventilation
01
Ventilation by Total Heat Exchanger
02
Bypass Ventilation
(No Total Heat Exchanging)
00
Not Available
01
Available
00
Not Used
01
(Use as 00 conditions)
00
Standard
01
30 min.
02
60 min.
00
Not Used
01
(Use as 00 conditions)
Not Available
00
01
60 min.
02
120 min.
6