5 Carefully check the installation by measuring the
earthing resistance with a earth resistance tester. If
the resistance is above the required level, drive the
electrode deeper into the ground or increase the
number of earthing electrodes.
6 Connect the earthing wire to the electrical component
box inside of the outdoor unit.
Step 13 Performing final check and
trial operation
1 Check the power supply between the outdoor unit
and the auxiliary circuit breaker.
• 1 phase power supply : L, N
• 3 phase power supply : R, S, T, N
2 Check the indoor unit.
a Check that you have connected the power and
communication cables correctly. (If the power
cable and communication cables one mixed up or
connected incorrectly, the PCB will be damaged.)
b Check that the thermistor sensor, drain pump/
hose, and display are connected correctly.
3 Press K1 or K2 on the outdoor unit PCB to run the
test mode and stop.
Key
Push type
1st
Heating test mode
K1
Short
2nd
Defrost test mode
3rd
1st
Cooling test
K2
Short
2nd
Inverter check
3rd
Pump down
K3
Short
1st
Release Eco mode
※ Defrost test mode
Condition 1: The outdoor temperature is below 10°C.
Condition 2: All the temperature conditions should meet
the defrost conditions.
360_AC_Outdoor_AU_Eng_EN.indb 21
Display
Mode
SEG
SEG
SEG
SEG
1
2
3
Stop
Reset
C type outdoor units
A / B type outdoor units
K1
4 After 12 minutes operation check discharged air
temperature of indoor unit
• Cooling mode (indoor unit check)  Inlet air temp.
- Outlet air temp.: From 10°C to12°C
• Heating mode (indoor unit check)  Outlet air
temp. - Inlet air temp.: From 11°C to 14°C
• In heating mode, the indoor fan motor can remain
off to avoid cold air blown into air-conditioned
space.
5 How to reset the power supply of the outdoor unit
and deactivate the eco mode (standby mode):
• Outdoor unit types A, B, and C: Refer to Outdoor
unit dimensions on page 6.
• Press K3 button over 1 sec to reset the power
4
supply of the outdoor unit and deactivate the eco
mode (standby mode).
※ Eco mode : Standby for minimizing power consumption
K1
K2
K3
K4
K2
K3
K4
English
2016-09-20 오후 8:00:34