Download  Print this page

Operation And Maintenance Requirements; Operations - Gefran SIEIDrive ADL300 Safety User Manual

Hide thumbs

Advertisement

6

Operation and maintenance requirements

6.1

Operations

Operations must comply with electrical precautions and ranges so far claimed and explained.
Following a table of the most important electrical drive precautions to comply with:
Signals
SAFETY ENABLE+, SAFETY ENABLE-
SAFETY OK1, SAFETY OK2
Input ENABLE HW_EN, DCOM
DRIVE OK-C, DRIVE OK-O
Digital Inputs
Encoder inputs
+24v, 0v24
PDS shall only be operated according to environmental conditions specified in device manual
herein reported.
Type
Max Installation Site
Altitude
Air Temperature
Relative Humidity
Contamination Levels
(IEN 60721-3-3)
Atmospheric Pressure
Vibration
(EN 60068-2-6)
(EN 60068-2-34)
Shock (EN 60068-2-29)
Free Fall
Approvals
Degree of pollution
Degree of protection
EMC
Any differences with respect to claimed operating conditions could overstress the device and
diminish the safety integrity of the system.
1S9STOEN_26-5-17_ADL300_STO_STO
Electrical safety constrains
Voltage shall not exceed 35v and shall not be inverted applied.
Voltage shall not exceed 125v. Current shall not exceed 250mA
Voltage shall not exceed 35v and shall not be inverted applied.
Voltage shall not exceed 125v. Current shall not exceed 250mA
Voltage shall not exceed 35v on any of the pins
Voltage shall not exceed 12v on any of the pins
Voltage Supply 24vDC shall not exceed 35vDC. It shall not be inverted
applied. It shall not be an AC voltage.
Operation
installed for stationary use
Up to 2000m
-10...50°C
5...85%
(Class 3k3 as per EN50178)
Boards without coating:
Chemical gases: n.a.
Solid particles:
no conductive
Boards with coating:
Chemical gases: n.a.
Solid particles:
no conductive
86 to 106 Kpa
(class 3K3 as per EN50178)
Sinus 10...150Hz 2g
2
Random 5....200 0,005g
no allowed
n.a.
Pollution degree 2 or better (free from direct sunligth, vibration, dust, corrosive or
inflammable gases, fog, vapour oil and dripped water, avoid saline environment)
IP54 for cabinet with externally mounted heatsink (size types 1007 and 3150)
Storage
in the protective package
-25...55°C
(class 1k4 EN50178)
5...95%
(Class 1k3 as per EN50178)
No condensation or icing allowed.
No conductive dust allowed.
Boards without coating:
Chemical gases: n.a.
Solid particles:
no conductive
Boards with coating:
Chemical gases: n.a.
Solid particles:
EN 60068-2-52: test Kb,
salt solution 5%, duration
test 24 h
86 to 106 Kpa
(class 1K4 as per EN50178)
n.a
Hz
n.a
250mm
CE
IP20
EN 61800-3
Transportation
in the protective package
-25...55°C
(class 2k3 EN50178)
5...95%
(Class 1k3 as per EN50178)
70 to 106 Kpa
(class 2K3 as per EN50178)
n.a.
n.a.
250mm
Pag. 22/30

Advertisement

Table of Contents

   Related Manuals for gefran SIEIDrive ADL300

Comments to this Manuals

Symbols: 0