Safety connector layout is shown in Figure 6
Table 3 is a description of signals onto Safety Connector.
Terminal
Signal name
name
EN+
+SAFETY ENABLE
EN-
-SAFETY ENABLE
OK1
SAFETY OK1
OK2
SAFETY OK2
-
Concerning the Regulation signals, the interface is more complex given the number of available
conFiguretions for ADL300:
ADL300 Basic the ENABLE signal is fixed onto the regulation board interface is shown in
Figure 8 and Table 6.
-
ADL300 Advanced, ENABLE and feedback signals are placed onto the ADL-IO expansion
card. ADL-I/O optional cards are listed in Appendix A.2 of Specification and Installation
User manual. Figure 10 and Table 7 show a sample example of ADL300 conFiguretion and
safety related pin description.
1S9STOEN_26-5-17_ADL300_STO_STO
Figure 6 Safety Connector Layout
Function Description
+24v for disabling the safety
function
0v COM for disabling the safety
function
Normally closed contact for Safety
feedback (contact 1)
Normally closed contact for Safety
feedback (contact 2)
Table 5 Description of Signals onto Safety Connector.
Electrical limits and range
(IN) +12...+35v with respect
to EN-
(IN) 0v
250mA maximum DC current
250mA maximum DC current
Pag. 17/30