Automatic Humidifier Control

Safety and Installation Instructions*
INSTALLER: R
EAD COMPLETE INSTALLATION INSTRUCTIONS BEFORE BEGINNING
. (
Throughout this document, the terms "Compustat" and "humidifier control"
INSTALLATION
are used interchangeably.)
WARNING: This product is for residential applications only, and must be installed by a qualified HVAC contractor.
Failure to comply could invalidate the product warranty, or result in serious injury or electrocution.
DANGER:
Disconnect electrical power to the furnace before beginning installation. Contact with a live electrical wire can cause
serious injury or electrocution.
Use caution when cutting plenum openings and handling ductwork. Sharp edges can cause serious cuts and bleeding.
CAUTION:
Do not mount Compustat on the supply duct or plenum. The unit will not withstand supply temperatures.
Do not mount Compustat downstream of the bypass outlet. Inaccurate humidity readings will cause the humidifier to
operate incorrectly.
When installing Compustat on downflow furnaces, make sure the blower continues to run after a heat call is satisfied,
to prevent high temperatures from damaging the control.
Do not set the humidity so high that condensation forms on windows or walls. Indoor condensation may result in
damage to the home.
*These instructions are for installation of the Skuttle Compustat humidifier control only. For installation of a
Skuttle humidifier, refer to the instructions packaged with the humidifier.
S
1:
TEP

Check Contents of Compustat Carton

Make sure the following components are present (see Figure 1):
Humidifier Control
Outdoor Temperature Sensor
Sensor Shield
S
2:
TEP

Disassemble the Humidifier Control

Pull the knob off, then remove the cover by inserting a screwdriver in the slot on the
right side of the control.
S
3:
TEP

Select an Interior Location and Mount the Control

Select a location to mount the humidifier control that is at least 6 inches upstream from
any of the following (see Figure 2):
Humidifier
Humidifier Bypass Ductwork (if applicable)
Fresh Air Intake Ductwork (if applicable)
Once a location has been selected, carefully position the humidifier control template, then
drill and cut the opening. Use four sheet metal screws and the gasket (provided) to mount
the control over the duct opening. Make sure the control is sealed tightly to the duct.
SEH-7100-000
Skuttle
Indoor Air Quality Products
by
®
Manual Mode Faceplate
Mounting Template
TM
Figure 1
Figure 2

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Compustat SEH-7100-000 and is the answer not in the manual?

Questions and answers

Summary of Contents for Skuttle Indoor Air Quality Products Compustat SEH-7100-000

  • Page 1: Automatic Humidifier Control

    • Do not mount Compustat on the supply duct or plenum. The unit will not withstand supply temperatures. • Do not mount Compustat downstream of the bypass outlet. Inaccurate humidity readings will cause the humidifier to operate incorrectly. • When installing Compustat on downflow furnaces, make sure the blower continues to run after a heat call is satisfied, to prevent high temperatures from damaging the control.
  • Page 2 For furnaces with accessory terminals… • If the accessory terminals provide 24 VAC, wire them to the “24 VAC” terminals on the humidifier control. • If the accessory terminals provide 120 VAC, wire them to a 24 VAC transformer; connect the transformer to the “24 VAC”...
  • Page 3 If an external transformer is used, connect a Model A50 relay in series with the solenoid valve and the “Out” terminals on the humidifier control. This will allow the humidifier to operate only when the furnace blower is on. (See Figure 6-8 to determine the correct wiring for your model humidifier).
  • Page 4: Troubleshooting Guide

    Compustat cover. Reattach the cover to the base and reinstall the knob. 1. To conduct a system test, be sure that 24 VAC is applied to the 24 VAC terminals of the humidifier control. 2. Reattach the Compustat cover and knob to the base.
  • Page 5 Similarly, Compustat will not operate if the indoor relative humidity exceeds 45 percent. • Check the humidifier control setting. If the relative humidity in the home is less than the knob setting, the humidifier will operate until the humidity level is higher than the knob setting.
  • Page 6 101 Margaret Street, Marietta, OH 45750 Phone: (800) 848-9786 Fax: (740) 373-9565 Email: customerservice@skuttle.com Web: www.skuttle.com...