PRODUCT DIAGNOSTICS
Alarms
ON-BATTERY
When the UPS is operating on the batteries, the On-Line LED will blink and the
audible alarm will sound every 10 seconds. The alarm will stop once the UPS
returns to On-Line operation.
UPS FAULT
When the UPS detects a hardware fault, the Fault LED will illuminate and the
UPS will emit a sustained tone. The fault condition can be reset by turning the
UPS OFF and then ON.
OVERLOAD
When the amount of load attached to the UPS exceeds its power rating, the
Overload LED will illuminate and the UPS will emit a sustained tone. This alarm
will remain on until the excess load is removed or the UPS self-protection circuit
shuts the UPS down.
REPLACE BATTERY
The UPS automatically tests the battery condition and will illuminate the
Weak/Bad Battery LED and emit a short beep. This tone will be repeated every
hour until the battery passes a self-test. It is recommended that the UPS be
allowed to charge overnight before performing a battery test to confirm a
Weak/Bad Battery condition.
LOW-BATTERY WARNING
The UPS will emit two consecutive beeps every five seconds when the battery
reserve runs low. This continues until AC returns or the UPS shuts down from
battery exhaustion.
18
PRODUCT DIAGNOSTICS
Communications Port
The communications port is a standard DB9 female with both RS232 and
simulated contact closure capability. The OmniGuard units will poll the port and
activate it for RS232 or contact closure in accordance with the type of cable it
finds connected to the port. Changing the port configuration requires that the
unit be turned off and restarted with the desired cable connected. The pin-out
for the port is depicted below.
DB9 Standard Pin-Out:
Pin 1: Battery low
Pin 2:
/TXD
Pin 3:
/RXD
Pin 4: UPS shutdown
Pin 5:
Ground
Pin 6:Instant off (Pull and hold this pin low to turn off the UPS.
Release this pin from low to restart the UPS.)
Pin 7:
Not used
Pin 8: AC fail signal
Pin 9:ATX wake-up signal