Parameterizing the digital outputs

In order to signal to the safety relay that the drive E-STOP function has been activated, the
following parameters must be set at the SINAMICS DC MASTER:
Digital output DO3 at connector X177.22 controls relay K
contact for the E-STOP path.
The function of DO3 (connector X177.22) is defined using parameter p50774:
p50774 = (63) r53100.0
Digital output DO2 at connector X177.21 controls, via relay K
The function of DO2 (connector X177.21) is defined using parameter p50773.
The setting of p50773 is dependent on the setting of parameter p50082:
p50082 = 0
p50082 = 1
p50082 = 2
p50082 = 3
p50082 = 4
p50082 = 21 (external field power unit, otherwise, as for setting
p50082 = 22 (external field power unit, otherwise, as for setting
p50082 = 23 (external field power unit, otherwise, as for setting
p50082 = 24 (external field power unit, otherwise, as for setting
Note
(63) signifies: "from own drive object"
r53100.0 is E-Stop state (1 = no E-Stop, 0 = E-Stop)
r53082.0 is CLOSE armature contactor
r53210.2 is auxiliaries ON
Note
The maximum 100 mA current rating of the digital outputs must be carefully observed.
Application document for functional safety STO, SS1 (ISO 13849-1)
Compact User Manual, 09/2016, A5E34871844AM
(no field)
(field is also switched with the armature contactor) p50773 = (63) r53082.0
(standstill field at ≥ o7.0)
(field is permanently switched on)
(field is also switched with the auxiliaries ON sig-
nal)
1)
3)
3)
4)
1.8 Parameterizing the digital outputs
. This serves as feedback signal
EP
, the field contactor.
DO2F
p50773 = 0
p50773 = 1
p50773 = 1
p50773 = (63) r53210.2
p50773 = (63) r53082.0
p50773 = 1
p50773 = 1
p50773 = (63) r53210.2