4.3.6
Standard Display Abbreviations:
The abbreviations will be seen during configuration or any alarm conditions.
Abbreviation
Wrt Prtd
Not Sprtd
Hi LMT
Low LMT
BAD-Tx
LKNWNGD
O/P Mode
RAM ERR
ROM ERR
FLW FLT
RAM CRC
BRW RST
NVM ERR
VCC FLT
SAT-LOW
SAT-HI
NO ERR
For notes saturation refer to section
Revision 2
Table 6: The Standard Display abbreviations
Meaning
"Write Protected"
Device is in write protect mode
"Not Supported"
Parameter is Not supported
"High Limit"
Parameter Value is greater than
high limit value
"Low Limit"
Parameter Value is less than low
limit value
"Bad Transmitter"
Transmitter is in critical condition
"Last known good value"
"Output Mode"
Device is in Output mode.
"Random Access Memory Error"
RAM corrupt
"Random Access Memory Error"
ROM corrupt
"Flow Fault"
Code Flow fault
"RAM Cyclic Redundancy Check"
RAM CRC failure
"Brown out reset"
"Non-Volatile Memory Error"
NVM corrupt
"VCC Fault"
Power supply fault
"Saturation High"
PV Value is in low saturation
condition
"Saturation Low"
PV Value is in high saturation
condition
No error
7.3.2
RMA803 Remote Indicator User's Guide
Recommended action
Change the mode to un protected and
then configure the device
The configuration is not supported. No
action.
Choose correct parameter value.
Choose correct parameter value.
Transmitter in critical fault. Correct the
transmitter.
Information only. It shows the last
measured good value when DE mode is
switched for Digital to analog. Please
note on a Digital to analog DE mode
change, power cycle is needed for the
mode change to be effective.
This is applicable for DE digital mode
only. See section 6 "Calibration" for
more details.
Hardware is faulty. Replace the
hardware
Hardware is faulty. Replace the
hardware
Hardware is faulty. Replace the
hardware
Hardware is faulty. Replace the
hardware
Power fluctuation is detected. To
recover, navigate to 'RMA DG' menu
and exit from Menu or power cycle the
device.
Hardware is faulty. Replace the
hardware
Power cycle the device or replace the
hardware
If the loop current value falls below 3.81
mA, Low saturation status is set. This is
an information only.
. If the loop current value is above 20.49
mA, High saturation status is set. This is
an information only.
Information only
22