Specifications & Accessories; Security Control; Compatible Devices - Honeywell ADEMCO VISTA Series Installation And Setup Manual

Hide thumbs Also See for ADEMCO VISTA Series:
Table of Contents

Advertisement

VISTA-15P/20P/SIA Installation and Setup Guide
Specifications & Accessories

Security Control

1. Physical: 12-1/2" W x 14-1/2" H x 3" D (318mm x 368mm x 76mm)
2. Electrical:
VOLTAGE INPUT: 16.5VAC from plug-in 25VA transformer, ADEMCO 1321 (in U.S.A.)
RECHARGEABLE BACKUP BATTERY: 12VDC, (sealed lead acid type); see Battery Table in
Mounting & Wiring section for proper battery sizes for various maximum current drains.
Charging Voltage: 13.8VDC.
ALARM SOUNDER: 12V, 2.0 Amp output can drive 12V BELLS or can drive one or two 702
(series connected) self-contained 20-watt sirens. Do not connect two 702s in parallel.
AUXILIARY POWER OUTPUT: 12VDC, 600mA max.
NOTE: For UL installations, Alarm Sounder plus Auxiliary Power currents should not
exceed 600mA total (500mA Aux, 100mA Bell Output).
FUSE (if installed): Battery (3A) No. 90–12 (PC board may have a PTC device instead of a
fuse. The PTC serves as an automatically resetting fuse.)
NOTE: This equipment shall be installed in accordance with the National Electrical Code,
ANSI/NFPA 70 and the National Fire Alarm Code, ANSI/NFPA 72.
3. Communication:
FORMAT SUPPORTED:
ADEMCO Express:
ADEMCO Low Speed: 10 pulses/sec, 1900Hz Data Tone, 1400Hz ACK/KISSOFF.
Radionics/SESCOA:
Ademco Contact ID
LINE SEIZE: Double Pole
RINGER EQUIVALENCE: 0.1B
FCC REGISTRATION No.: 5GBUSA-44003-AL-E
4. Maximum Zone Resistance:
SIA Minimum Hardware Configuration: 1 model VISTA-20PSIA/15PSIA control panel, and 1 6160V keypad,

Compatible Devices

Keypads:
Wireless Receivers:
Zone Expansion:
Relay Module:
Communication
Device:
10 characters/sec, DTMF (TouchTone) Data Tones,
1400/2300Hz ACK, 1400Hz KISSOFF.
20 pulses/sec, 1800Hz Data Tone, 2300Hz ACK/KISSOFF.
Can report 0-9, B-F
10 characters/sec., DTMF (TouchTone) Data Tones,
1400/2300Hz ACK, 1400Hz KISSOFF.
Zones 2–8 = 300 ohms excluding EOLR standard zones
Zone 1 = 100 ohms excluding EOLR
and 1 UL Listed Bell.
6150 Fixed-Word Keypad, 6160 Alpha Keypad, 6150V and
6160V Voice Keypads, 6280 Touch Screen Keypad,
Tuxedo Touch Advanced User Interface (AUI)
5881ENL: accepts up to 8 transmitters
5881ENM: accepts up to 16 transmitters
5881ENH: accepts up to system maximum transmitters
5883H Transceiver: accepts up to system maximum transmitters
6150RF Keypad/Transceiver: accepts up to 16 transmitters
6160RF Keypad/Transceiver: accepts up to system maximum trans.
4219 WIRED EXPANSION MODULE
4229 WIRED EXPANSION/RELAY MODULE
4204 RELAY MODULE
7847i, 7847i-E, LTE-iV, LTE-iA, LTE-XV, LTE-XA, LTE-XCgsm