BACnet/IP MODULE

(BIP option)

Specifications

Ethernet Port : 10/100-compatible with 10 Base-T interface, RJ-45
Visual Indicators :
Network Configuration: See 301C BACnet menu section.
BACnet/IP protocol
UDP Port: 47808. This value is not modifiable using the 301C.
The module has been developed as per ANSI/ASHRAE Standard 135-
2001 : BACnet®— A Data Communication Protocol for Building
Automation and Control Networks. The Data Link Layer option is per
BACnet/IP (Annex J).
http://www.ashrae.org/

BACnet Objects

BACnet objects represent any information available through the 301C
sub network. Each available value is represented by one object of a
specific type. There are currently 6 object types supported :
Analog Input
Analog Value
Binary Input
Binary Output
Binary Value
Device
510324
4/07
Green LED
Yellow LED
represented by 'AI'
represented by 'AV'
represented by 'BI'
represented by 'BO'
represented by 'BV'
represented by 'DEV'
301C User Manual
Honeywell
LINK
ACT
BACnet/IP MODULE
93