The Sentry controller is the heart of the Sentry Gas Risk
Management system. It is a microprocessor based sys-
tem that performs functions including management of the
sensor modules, management of alarm relays and inter-
face with the user via the front panel display, printer out-
put, Modbus digital communication, alarm indicators and
relay outputs.
Sentry system two-way communication between the sen-
sors and the controller results in the capability to perform
one-person calibration and diagnostic checks from the
controller. The user-friendly front panel includes a large
display of the gas concentration and sensor number. Vari-
ous scan modes are available to meet the user's specific
monitoring needs. A separate 2-line alphanumeric dis-
play provides more detailed information including sensor
data, error messages and menu prompting for calibration
and set-up.
A series of alarm LEDs instantly inform the user of alarm
status on any of the eight sensors interfaced to the con-
troller. These LEDs are solid for low alarm and flashing for
high alarm. A trouble LED warns that one of 120 diagnos-
tic checks has detected a problem. More information about
the trouble will be displayed on the alphanumeric display.
A calibrate/change LED indicates that calibration or con-
Sierra Monitor Corp. 1991 Tarob Ct., Milpitas, CA 95035, USA, 408-262-6611, 800-727-4377, FAX: 408-262-9042
Web Site: http://www.sierramonitor.com
figuration change is being performed on at least one sen-
sor. The remaining sensors will remain on-line providing
continuous protection.
The Sentry keypad, together with the user-friendly menu
on the alphanumeric display, guides the user through set-
up, calibration and maintenance of the Sentry system.
E-Mail: sales@sierramonitor.com
© 2009 by Sierra Monitor Corporation
Sentry
Controller

Advertisement

Table of Contents
loading

  Also See for Sierra Monitor Corporation Sentry 5000

  Related Manuals for Sierra Monitor Corporation Sentry 5000

  Summary of Contents for Sierra Monitor Corporation Sentry 5000

  • Page 1 The remaining sensors will remain on-line providing continuous protection. The Sentry keypad, together with the user-friendly menu on the alphanumeric display, guides the user through set- up, calibration and maintenance of the Sentry system. E-Mail: sales@sierramonitor.com © 2009 by Sierra Monitor Corporation Sentry Controller...
  • Page 2 Key Event Report to print. E-Mail: sales@sierramonitor.com Sentry Controller – a snap– PRESENT CONFIG.: STATUS = 07 DAYS – lists all PRESS ENTER TO: [SYSTEM REPORT] prints when any sensor module read- © 2009 by Sierra Monitor Corporation...
  • Page 3 Combustible Gas* Sulfur Dioxide Oxygen* Nitrogen Dioxide Hydrogen Sulfide* Hydrogen Chloride Carbon Monoxide* Hydrogen Cyanide Chlorine* Ammonia* Hydrogen Nitric Oxide Hydrogen Fluoride Methane / Propane * Refer to IT Series Data Sheet E-Mail: sales@sierramonitor.com © 2009 by Sierra Monitor Corporation...
  • Page 4 143.0 pounds (65.0 kg) FM Approved, CE Mark Shelf for insertion in Instrument Cabinet Panel bracket, bezel Wall or vertical surface Explosion Proof, Class 1, Div I, Group C & D INSTRUMENT RACK PRINTER RACK MOUNT tolerant) © 2009 by Sierra Monitor Corporation...