GENERAL INFoRMAtIoN
This appliance has been tested for capacity and efficiency
in accordance with AHRI Standards and will provide many
years of safe and dependable comfort, providing it is properly
installed and maintained. Abuse, improper use, and/or
improper maintenance can shorten the life of the appliance
and create unsafe hazards. Please read all instructions
before installing the unit.
Before You Install this unit
√ This equipment is securely packaged at the time of
shipment and upon arrival should be carefully inspected
for damage prior to installing the equipment at the job
site. Claims for damage (apparent or concealed) should
be filed immediately with the carrier.
√ it is recommended that the cooling load of the area to
be conditioned should be calculated and a system of the
proper capacity selected.
√ Check the electrical supply and verify the power supply
is adequate for unit operation. The system must be wired
and provided with circuit protection in accordance with
local building codes. If there is any question concerning
the power supply, contact the local power company.
√ Verify the duct system is appropriate for the air handler
being installed. Please note that when replacing an existing
system with lower air-flow, the duct system may require
modification.
Locating the Air Handler
• Survey the job site to determine the best location for
mounting the unit. Consideration should be given to
availability of electric power, service access, and noise.
• The dimensions of the room or alcove must be able to
accommodate the overall size of the unit and the installation
clearances listed in
Table
1. Physical dimensions for this
air handler are also shown in
Figure 12 (page
15).
• The air handler should be set into position before routing
the refrigerant tubing.
Minimum clearances
• This appliance must be installed in accordance with
clearances listed in
Table
1. The air handler must be
installed with ample clearance for easy access to the air
filter, blower assembly, heater assembly, controls, and
vent connections. Applicable building codes may require
additional clearance to equipment. Refer to applicable
building codes for details.
• Static pressure drop through louvered openings and
through return air plenums should be considered in the
overall duct design in the determination of the total external
static pressure.