 Setup → Advanced setup → Switch output → Switch-off delay
• Switch output function (→  194) = Limit
• Assign limit (→  195) ≠ Off
Defines the delay applied before the output is switched off.
0.0 to 100.0 s
0.0 s
 Setup → Advanced setup → Switch output → Failure mode
Switch output function (→  194) = Limit or Digital Output
Defines the state of the switch output in case of an error.
• Actual status
• Open
• Closed
Open
 Setup → Advanced setup → Switch output → Switch status
Current status of the switch output.
 Setup → Advanced setup → Switch output → Invert output signal
' N o' The switch output behaves as per its parameter setting. ' Y es' The switching behavior is
inverted as compared to its parameter setting.
• No
• Yes