STRYKER VAV ZIO CONFIGURATION

ZIO CONFIGURATION SCOPE

This document serves as a technical users guide for an
installer who is configuring a Stryker VAV controller via a
TR71 or TR75 wall module. Parameters are grouped into
logical categories rather than on large list. To access the
"Contractor" mode for configuration, press the Up, Down and
middle keys simultaneously. During this time the model
number and firmware revision of the TR71/75 will be displayed
and then you will be prompted to enter a password (default
0000) to enter the Contractor mode. You can then navigate to
the desired category of parameters and then begin
configuring and viewing information from the device. Each
screen below has a brief explanation of the data, and in cases
where the data can be changed, the corresponding network
variable is shown in brackets. For example, the "MAX FLOW"
parameter that is found in the "BALANCE" category is
manipulating the MaxMeasFlowAct section of the
nciBalanceSetPts structured nci and is noted as
[nciBalanceSetPts, MaxMeasFlowAct]. Values within the
Contractor mode are only viewable in English (U.S.) units of
measure. Temperatures however CAN be shown on the home
screen as C or F.
Controller Features NOT Supported by Zio Configuration
• Network Functionality
• Accessory Loops
• Custom Sensors
• Local Sensor (UI 1-4) Calibration
VAV Controller Default Configuration
Wall Module = Zio
Center SetPoint Source: Zio
Center SetPoint: Disabled (controller ignores center setpoint
value)
Center SetPoint High Limit: 100
Center SetPoint Low Limit: -10
Room Temperature Source = Zio (TR71/75)
Pressure independent flow control
Temperature Control = Cooling Only
Floating Damper Motor:
Connected to DO3 & DO4
90 sec travel time
63-2730—01

HOME SCREEN OPTIONS

Center SetPoint, Outside Air & Room Temperature (setpoint is
adjustable from Home Screen)
Room, Outside Air Temperature & Center SetPoint (setpoint is
adjustable from Home Screen)
Center SetPoint Temp (setpoint is adjustable from Home
Screen)