GE AF-650 GP Operating Instructions Manual page 60

High power unit sizes 6x
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

ALARM 93, Dry pump:
A no-flow situation and high speed indicate that the pump has run dry. See
parameter group AP-2#.
ALARM 94, End of curve:
Feedback stays lower than the setpoint which may indicate leakage in the
pipe system. See parameter group AP-5#.
ALARM 95, Broken belt:
Torque is below the torque level set for no load, indicating a broken belt. See
parameter group AP-6#.
Warning 96, Start Delayed:
A start signal is suppressed because the time that has passed since last ac-
cepted start is less than the minimum time programmed in par. AP-76 Interval
between Starts.
Warning 97, Stop Delayed:
A stop signal is suppressed because the motor has been running less time
than the minimum time programmed in par. AP-77 Minimum Run Time.
WARNING 98, Clock fault:
Clock Fault. The time is not set or the RTC clock (if mounted) has failed. See
parameter group K-7#.
WARNING 200, Fire mode:
The input command fire mode is active. See parameter group FB-0#.
WARNING 201, Fire mode was active:
Fire mode has been active. See parameter group K-7#.
WARNING 202, Fire mode limits exceeded:
One or more warranty voiding alarms have been suppressed during fire mode
operation. See parameter group K-7#.
ALARM 243, Brake IGBT:
This alarm is only for unit size 6x frequency converters. It is equivalent to Alarm
27. The report value in the alarm log indicates which power module generated
the alarm:
1 = left most inverter module.
2 = middle inverter module in 62 or 64 drive.
2 = right inverter module in 61 or 63 drive.
3 = right inverter module in 62 or 64 drive.
5 = rectifier module.
ALARM 244, Heatsink temperature
This alarm is only for unit size 6x frequency converters. It is equivalent to Alarm
29. The report value in the alarm log indicates which power module generated
the alarm:
1 = left most inverter module.
2 = middle inverter module in 62 or 64 drive.
2 = right inverter module in 61 or 63 drive.
3 = right inverter module in 62 or 64 drive.
5 = rectifier module.
ALARM 245, Heatsink sensor
This alarm is only for unit size 6x frequency converters. It is equivalent to Alarm
39. The report value in the alarm log indicates which power module generated
the alarm:
1 = left most inverter module.
2 = middle inverter module in 62 or 64 drive.
2 = right inverter module in 61 or 63 drive.
3 = right inverter module in 62 or 64 drive.
5 = rectifier module.
High Power Service Manual for Unit Sizes 6x
ALARM 246, Power card supply
This alarm is only for unit size 6x frequency converters. It is equivalent to Alarm
46. The report value in the alarm log indicates which power module generated
the alarm:
1 = left most inverter module.
2 = middle inverter module in 62 or 64 drive.
2 = right inverter module in 61 or 63 drive.
3 = right inverter module in 62 or 64 drive.
5 = rectifier module.
ALARM 247, Power card temperature
This alarm is only for unit size 6x frequency converters. It is equivalent to Alarm
69. The report value in the alarm log indicates which power module generated
the alarm:
1 = left most inverter module.
2 = middle inverter module in 62 or 64 drive.
2 = right inverter module in 61 or 63 drive.
3 = right inverter module in 62 or 64 drive.
5 = rectifier module.
ALARM 248, Illegal power section configuration
This alarm is only for unit size 6x frequency converters. It is equivalent to Alarm
79. The report value in the alarm log indicates which power module generated
the alarm:
1 = left most inverter module.
2 = middle inverter module in 62 or 64 drive.
2 = right inverter module in 61 or 63 drive.
3 = right inverter module in 62 or 64 drive.
5 = rectifier module.
ALARM 250, New spare part:
The power or switch mode power supply has been exchanged. The frequency
converter model number must be restored in the EEPROM. Select the correct
model number in par. SP-23 Typecode Setting according to the label on the
unit. Remember to select 'Save to EEPROM' to complete.
ALARM 251, New model number:
The frequency converter has got a new model number.