Mdcic Mounting Panel - GE AF-650 GP Operating Instructions Manual

High power unit sizes 6x
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

7.2.7 MDCIC Mounting Panel

1.
Remove top mounted safety cover from inverter module by removing attaching screws (8mm).
2.
Disconnect ribbon cable from control card.
3.
Before removing MDCIC ribbon cable from each inverter module, note which cable connects to each module for reassembly. Remove MDCIC ribbon
cable from each inverter module.
4.
Before removing rectifier control cable MK101 of MDCIC board, note for reinstallation that MK101 is left most 6-pin connector on MDCIC board. Remove
rectifier control cable from MDCIC board.
5.
Remove relay connector from MDCIC panel.
6.
Remove any customer interconnect wiring.
7.
Remove MDCIC panel by removing four screws (M5) attaching panel to inverter cabinet (one in each corner of panel).
7
7
4
1
MDCIC mounting panel
2
Relay connector (not shown) (step 5)
3
MDCIC board cover plate
4
Attaching screw (step 7)
Reinstall in reverse order of this procedure.
104
1
High Power Service Manual for Unit Sizes 6x
130BX268.10
5
Rectifier control cable MK101 (step 4)
6
MDCIC ribbon cable (step 3)
7
Control card to MDCIC ribbon cable (step 2)
2
3
4
5
6

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Af-600 fp

Table of Contents